Owners Manual

7
Location Requirements
WARNING
Explosion Hazard
Keep flammable materials and vapors, such as gasoline,
away from appliance.
Use nonflammable cleaner.
Failure to do so can result in death, explosion, or fire.
Ventilation and Clearance
Keep flammable materials and vapors, such as gasoline, away
from freezer.
Do not cover the freezer with items such as blankets, sheets,
and tablecloths. This reduces air circulation.
Allow at least a 3” (7.5 cm) clearance on both sides of the
freezer and 2” (5 cm) between the back of the freezer and the
wall. If the freezer is to be next to a fixed wall, leave extra
space on the hinge side so the door can open wider.
Temperature
Your freezer operates most efficiently when located in an area
where the temperature will not fall below 40°F (5°C). Place your
freezer in a location where the temperature will not fall below this
recommended temperature.
Upon Moving to Final Location
Below dimensions are applicable for Upright Freezers of 16",
18", 20" when they are not side kicks.
For Side Kicks and Refrigerators refer below informations
NOTE: This freezer may be installed side by side with another
freezer or refrigerator. Allow for a 1" (2.54 cm) space behind the
freezer and a 1/4" (6.4 mm) clearance between the appliances.
Water Supply Requirements (on
some models)
Gather the required tools and parts before starting installation.
Read and follow the instructions provided with any tools listed
here.
Tool Needed:
Flat-blade screwdriver
7/16" and 1/2" open-end or
2 adjustable wrenches
1/4" nut driver
1/4" drill bit
Cordless drill
NOTE:
Your freezer dealer has a kit available with a 1/4" (6.35 mm)
saddle-type shutoff valve, a union, and PEX tubing. Before
purchasing, make sure a saddle-type valve complies with your
local plumbing codes. Do not use a piercing-type or 3/16"
(4.76 mm) saddle valve which reduces water flow and clogs more
easily.
IMPORTANT:
If you turn on the freezer before the water line is connected,
turn off the ice maker.
All installations must meet local plumbing code requirements.
Use PEX tubing and check for leaks. Install PEX tubing only in
areas where temperatures will remain above freezing.
Water Pressure
A cold water supply with water pressure between 30 and 120 psi
(207 to 827 kPa) is required to operate the water dispenser and
ice maker. If you have questions about your water pressure, see
“Troubleshooting” online or call a licensed, qualified plumber.
Reverse Osmosis Water Supply
If a reverse osmosis water filtration system is connected to your
cold water supply, the water pressure to the system needs to be a
minimum of 40 to 60 psi (276 to 414 kPa).
If the water pressure to the reverse osmosis system is less than
40 to 60 psi (276 to 414 kPa), a booster pump can be inserted into
the small tubing that goes from the cold water line to the reverse
osmosis system.
If the water dispenser is still not dispensing water properly:
Check to see whether the sediment filter in the reverse
osmosis system is blocked. Replace the filter if necessary.
Allow the storage tank on the reverse osmosis system to refill
after heavy usage.
If your refrigerator has a water filter, it may further reduce the
water pressure when used in conjunction with a reverse
osmosis system. Remove the water filter.
If you have questions about your water pressure, refer to
“Troubleshooting” online or call a licensed, qualified plumber.
Connect the Water Supply
Connect to Water Line
1. Unplug freezer or disconnect power.
2. Turn off main water supply. Turn on nearest faucet long
enough to clear line of water.
3. Locate a 1/2" to 1 1/4" (12.7 mm to 3.18 cm) vertical cold
water pipe near the freezer.
IMPORTANT:
Make sure it is a cold water pipe.
Horizontal pipe will work, but drill on the top side of the pipe,
not the bottom. This will help keep water away from the drill
and normal sediment from collecting in the valve.
4. Determine the length of copper or PEX tubing you need.
Measure from the connection on the lower-left rear of freezer
to the water pipe. Add 7 ft. (2.1 m) to allow for cleaning. Use
1/4" (6.35 mm) O.D. (outside diameter) copper or PEX tubing.
Be sure both ends of copper or PEX tubing are cut square.