Installation manual
INSTALLATION 
8  May 2010 / M-SC3.5 / EN 
4  SIPHON BREAKER (AIR VENT) 
When the point of water injection is below the waterline, 
then -when the engine is stopped -there is a risk that the 
cooling water may enter the engine as a result of 
siphoning. To avoid this happening, the generating set is 
designed to accommodate a siphon breaker (air vent). In 
the standard delivery the connections are bypassed. Hose 
of 12.5 mm (1/2") inner diameter should be used. If the 
generating set cannot be mounted such that the bottom of 
the generating set is placed above the waterline, an air 
vent must be installed. Extend the water hose of the by-
pass 600 mm above waterline and install an air vent. 
Ideally, the air vent should be mounted above the yacht 
keel center line (i.e. to minimize the influence of swaying 
on the water intake). The hose of the drain should go 
downwards. Water must flow out freely and air has to flow 
in freely as well (refer to figure 7). 
Fast motorboats will lay deeper when sailing at large 
speed and can cause pressure on the waterinlet. This 
should be avoided to prevent fleeding the engine. If the air 
vent is clogged the water hoses will not be vented when 
the generating set has stopped and water can be forced 
into the engine. This leads to immediate engine problems 
and eventually severe damage! 
DAMAGE CAUSED BY THE INGRESS OF 
WATER IN THE ENGINE IS NOT COVERED 
BY WARRANTEE 
On the valve is a little hose to drain a little water that could 
be spilled from the valve. This hose should go down and 
may not end under water, because it should ventilate air 
into the valve to break the siphoning (figure 7). 
Figure 7: Wrong siphon breaker hose routing 
Check the air vent at regular intervals. Open, clean and 
lubricate the valve as required (figure 8). 
Figure 8 










