Technical information
OPERATION 
18  May 2010 / M-SC3.5 / EN 
3 OPERATION 
3.1 GENERAL  
The generating set is operational after full installation and 
filling up with: fuel, engine lubricating oil and cooling liquid, 
filling the starter battery with acid, connecting the battery 
to earth and connecting the MasterView Easy remote 
panel. 
1 Filling cap; 
2  Minimum oil level; 
3  Maximum oil level. 
Figure 9 
3.2 OPERATING INSTRUCTIONS  
3.2.1  Summarised operating instructions (daily 
use) 
Routine "pre-start" checks: 
1  Check oil level (refer to figure 9). 
2  Engine cooling system (all valves open). 
3 Power source selector switch (off/shore 
power/generator power). Switch power source switch 
to "OFF", or switch off all consumers in the usual way. 
If a Masterswitch  is installed, this operates 
automatically. 
4  Switch on battery switch (when installed). 
5  Fuel valve: open. 
Starting: 
To initiate the full automatic starting procedure, push 
the Start / Stop button on the Local control panel or 
give a start command by means of the MasterView 
Easy. You can monitor the procedure on the display 
of the MasterView Easy. 
In operation checks: 
1  Check for abnormal noise or vibration; 
2  Check the voltage; 
3  Check sea water flow at exhaust outlet; 
4 Power source selector switch (off/shore 
power/generator power). Switch to power source 
Generator. If a Masterswitch is installed, this operates 
automatically; 
5  Before loading the generating set up to maximum, 
have it run warm. Continuous load should be 
restricted to 70 % of maximum load. 
Stopping generator: 
1  Switch off all electrical devices (consumers). If the 
generating set has been running under full load for a 
longer period, do not shut it down abruptly. Reduce 
the electrical load to about 30% of the rated load (i.e. 
30% of 3 kW is approx. 1000W) and let it run for 
approx. 5 minutes; 
2  Push the Start / Stop button on the Local control panel 
or give a stop command by means of the MasterView 
Easy; 
3  Close the inlet sea water cock; 
4  Switch to an other 230V power source, if available. If 
a Masterswitch is installed, this is done automatically. 
3.2.2  Extended operating instructions  
Check when starting the first time or after a longer period 
of rest: 
1  If there is any damage caused by transport or 
installation. 
2  Check if installation conforms to the installation 
instructions. 
3  Ensure the generating set is free to turn without 
obstruction. 
4  Check all hoses and hose connections for leaks. 
5  Check all cables and cable end terminal connections. 
6  Check the engine and generator mounting bolts. 
Routine "pre-start" checks: 
1  Check engine oil level. 
The generator switches off in the event of insufficient 
oil-pressure. Even when the oil level is too low the oil 
pressure can be high enough. Do not run the 
generator with the oil below the lowest mark in the, 
because a smaller volume of oil will become 
contaminated considerably quicker than a larger 
volume. Therefore we recommend daily oil-checks. 
Check oil level prior to starting the engine or at least 5 
minutes after the engine has stopped. 
2  Check sea water cocks. Do not forget the valve of the 
water outlet in case of a water/exhaust gas separator. 
3  Check the water strainer. 
4  Check for leaks. 
5  Regularly check the siphon vent in the cooling water 
supply. 










