Technical information
TROUBLE SHOOTING   
24  May 2010 / M-SC3.5 / EN 
5 TROUBLE SHOOTING 
5.1  ALTERNATOR/ ELECTRICAL FAULTS 
Beware of parts which are live! 
Before working on the generator, remove the 
30Amp fuse from the local control panel (see 
figure 3) to prevent the engine from starting. 
5.1.1 General  
If any problem should occurs, check basic conditions and 
examine all external wiring, switch gear and circuit 
breakers. Also check if measuring instruments give the 
correct value. If in doubt, measure directly on the 
alternator terminals with an independent instrument. This 
should only be carried out by an experienced electrician. 
Check if the engine is running correctly at 3000 (50 Hz) 
RPM according to its settings and does as well under load. 
A RPM drop of 5% at full load is acceptable. Therefore a 
no load setting should be at 3150 RPM = 52.5 Hz. Under 
no circumstances should the RPM under full load be below 
2940 RPM = 49 Hz 
When the problem is in the RPM refer to section 5.2. 
When the generator was stopped due to an electrical 
failure, the origin of the failure that stopped the generator 
will be displayed on the MasterView Easy remote control 
panel. See section 5.1.2. 
See section 5.1.3 for other electrical faults. 
5.1.2  Failure or warning messages displayed on the remote control panel 
AC warnings and failures  Meaning  What to do? 
No failure  None (no failure detected)  -- 
UAC Low  Generator output voltage too low  See section 5.1.3 
UAC High  Generator voltage too high  See section 5.1.3 
IAC High  AC output current is too high  Reduce connected load or see 
section 5.1.3 
FAC Low 
AC output frequency is too low, engine speeds is 
too low 
See section 5.2.3 
FAC High 
AC output frequency is too high, engine speed is 
too high 
See section 5.2.3 
Overload 
Too much load connected to the AC output of 
the generator 
Reduce connected load or see 
section 5.1.3 










