Technical information
    TROUBLE SHOOTING 
EN / M-SC3.5 / May 2010  27 
PROBLEM  POSSIBLE CAUSE  WHAT TO DO? 
Generator is not able to start an 
electric motor. 
If the generator is unable to supply 
enough power to start an electric motor 
(230V), this is usually because this motor 
draws too much current during starting. 
Check the electric motor’s current draw 
required for starting. This should not exceed 
70% of the rated generator output current. This 
could be remedied by providing stronger 
capacitors to the motor or using a "soft-start". 
Inquire at your nearest Whisper Power dealer 
or directly at the manufacturer, Whisper Power 
in the Netherlands. 