Product Overview

www.white-rodgers.com
142
HYDRONIC
HYDRONIC
CONTROLS
SPECIFICATIONS
Dimensions. . . . . . . . . . . . . . . . . . . . . . . . (1145-33) 5
3
/
8
H x 2
5
/
16
W x 1
7
/
8
D
(11A79-2) 5
3
/
8
H x 2
5
/
16
W x 1
7
/
8
D
Bulb Extensions . . . . . . . . . . . . . . . . . . . . Element has
1
/
2
pipe threads
(1145-33) 11
3
/
16
beyond threads
(11A79-2) 3
3
/
8
beyond threads
Finish . . . . . . . . . . . . . . . . . . . . . . . . . . . . Grey
Agency . . . . . . . . . . . . . . . . . . . . . . . . . . . U.L. listed and C.S.A. certied
FAST RESPONSE DIRECT IMMERSION CONTROLS
1145-33 Control has Thermal Element Immersed Directly in the
Water for use as a High Limit and/or Operating Control. 11A79-2 for
Immersion Directly in the Boiler Water. Use as a High Limit, Low Limit,
Circulator Control or Combination Low Limit and Circulator Control.
FEATURES
Specially designed hydraulic action element for fast response to temperature
change.
Temperature dial calibrated in °F and °C and can be adjusted through cover.
Control mounts in any position without affecting performance.
3
/
4
bushing furnished with each control.
Full Motor Rating Valves and
Model Switch Electrical (Full Load) Relays
Number Range Differential Thread Size Action Rating 120 VAC 240 VAC 24 VAC 0.3-12v DC
1145-33 100 to 240°F 5 to 45°F ½ Open on Rise HTV 10.0A 6.0A 6.0A 1.0A
(38 to 116°C) (3 to 25°C) See page 416
11A79-2 100 to 240°F 7 to 45°F ½ SPDT HH 7.4A 3.7A 2.9A
(38 to 116°C) (4 to 25°C) See page 416
Dial has U.L. approved adjustable stop, factory pre-set at 185°F (85°C) maximum setting.
Dial has U.L. approved adjustable stop, factory pre-set at 220°F maximum.
PARTS AND ACCESSORIES See end of this section for parts and accessories
1145-33
11A79-2
CONTRACTOR TIP: TESTING AUTOMATIC TEMPERATURE CONTROLS To verify a control is opening and closing properly, disconnect
all power before testing. Testing must be performed with the sensing element at a temperature within the setting range of the control. For
most hydronic controls with a range of 100 to 240°F, a pan of hot water is sufcient to reach the control range.
Attach an ohmmeter or continuity tester across the Open on Rise contacts. Lower the temperature setting dial to the lowest setting.
If the lowest setting is below the temperature of the sensing element minus the differential of the control, the contacts should be open.
Raise the temperature dial slowly. When the setting is raised above the temperature of the sensor, the contacts should close.