Product Overview

True Champions
WHITE-RODGERS “1300” SERIES HYDRONIC ZONE VALVES
St. Louis, Missouri • Markham, Ontario
www.white-rodgers.com
Hydronic Zone Valves
FOR HIGH AND LOW CAPACITY APPLICATIONS
There are two types of White-Rodgers “1300” series zone valves available, 2-wire and
3-wire, for zoning hydronic systems up to 50 PSI. The valves operate quietly and efficiently
providing you with comfort and reliability.
The valve stem is made of a corrosion resistant stainless steel and has a self aligning barrel-type design, which
uses line pressure to seal off without binding on opening and closing.
The motor can easily be removed from the valve assembly without draining the system, meaning less mess for
you. Automatic recycling manual operator shows valve position at all times. Screw terminal wiring panel for
added convenience. Built-in auxiliary contacts to control burner or circulator relay.
1311 SERIES SELECTION CHART
• 3-wire
24V thermostat circuit rating 0.4A (valve current is
0.4A only during opening or closing. For proper
anticipation, select thermostat designed for use
with a 3-wire zone valve)
• Time cycle: 45 seconds/open; 45 seconds/close
1361 SERIES SELECTION CHART
• 2-wire
• 24V thermostat circuit rating 0.2A (valve current
is 0.52A when opening but 0.2A when fully open;
therefore set anticipator for 0.2A)
• Time cycle: 45 seconds/open; 60 seconds/close
REPLACEMENT PARTS
Model Tubing Friction Loss Equivalents
Number Size
Cv Factor Ft. of Tubing
PMax P. Temp.
(I.D. Pipe)
1311/1361 – 102 3/4 23.5 2-1/2 15 PSI 50 PSI 240ºF (116ºC)
1311/1361 – 103 1 37.0 4 15 PSI 50 PSI 240ºF (116ºC)
1311/1361 – 104 1-1/4 42.2 7 15 PSI 50 PSI 240ºF (116ºC)
Model No. Description
F19-0737 Replacement motor with bracket and leads
F19-0190 Replacement motor only (for all models)
Z12ADINV Adaptor, inverted flare pipe to 1/2sweat
Z34ADINV Adaptor, inverted flare pipe to 3/4 sweat
Z1ADINV Adaptor, inverted flare pipe to 1 sweat
Z12ADFL Adaptor, flare pipe to 1/2 sweat
Z34ADFL Adaptor, flare pipe to 3/4 sweat
Z1ADFL Adaptor, flare pipe to 1 sweat