Catalog Page

50A55-3797 Replaces:
Trane White-Rodgers
CNT02789 50A55-474
CNT02891 50A55-476
CNT03799 50A55-571
D341122P01
D341235P01
D341235P03
TRANE
INTEGRATED HSI MODULE
DIRECT
REPLACEMENT
50A55-3797
CROSS REFERENCE
Model
Number
Pre-Purge
Time
Heat Delay-
To-Fan-On
Heat Delay-
To-Fan-Off
Cool Delay-
To-Fan-On
Cool Delay-
To-Fan-Off
Post
Purge
50A55-3797
0 sec 45 60 / 100 / 140 / 180 2 0 / 180 5 sec
50A55-3797 TRANE SINGLE STAGE 120V IGNITION
INTEGRATED HSI FURNACE CONTROL
ControlsGasValve,Ignitor,Blower,Inducer,Humidier(120V),
and Air Cleaner. Replaces OEM Trane and White-Rodgers Models
FEATURES
•Includesashcodediagnostics.
•Fusedtoprotectlowvoltagesystemtransformers.
SPECIFICATIONS
Operating Temperature................... -40 to 176°F
Humidity Range ........................ 5% to 93% RH (non-condensing)
Mounting.............................. Snap in standoffs
Electrical Ratings @ 77°F (25°C)
Input Voltage........................... 25 VAC 50 / 60 Hz
Maximum Input Current @ 30 VAC ......... 0.45 amp
Relay Load Ratings
Valve Relay............................ 1.5 amp @ 25 VAC 50 / 60 Hz 0.6 pf
Ignitor Relay ........................... 6.0 amp @ 120 VAC 50 / 60 Hz
Inducer Relay .......................... 2.2 FLA-3.5 LRA @ 120 VAC
Circulator Relay ........................ 14.5 FLA-25.0 LRA @ 120 VAC
Flame Current Requirements
Minimumcurrenttoinsureamedetection.... 1 uA DC
Maximum current for non-detection ......... 0.10 uA DC
Maximumallowableleakageresistance...... 100 M ohms
Timing Spec (@ 60 Hz) maximum
Flame establishing time .................. 0.8 sec
Flame failure response time ............... 2.0 seconds
NOTE:At50Hz,alltimingspecicationsshouldbeincreasedby20%.
NOTE: Can also use Universal Kit 50M56U-843
New
www.white-rodgers.com
53
HEATING

Summary of content (1 pages)