Brochure

www.white-rodgers.com
95
FURNACE
R
W
Type 24A06 Dual Level Temp
White
Bimetal
Heater #1
Switch #1
Switch #2
Bimetal
Heater #2
Transformer
2-Wire
Heating
Thermostat
Black w/ Red Stripe
Red w/ Black Stripe
L1
Line
L2
L1
Line
L2
Heating
Load #2
Heating
Load #1
Red
Black
Blue
Black w/
White Stripe
Red
Line Voltage
Low Voltage
Line Voltage Field
Low Voltage Field
WIRING
LEVEL-TEMP LOW VOLTAGE
CONTROL SYSTEMS FOR ELECTRIC HEAT
Provides Silent Operation and Narrow Differential Control for Heating
or Cooling Installations for use with a 2-Wire 24 Volt Thermostat
SPECIFICATIONS
Dimensions Models 24A01/05 . . . . . . . . . 1
7
/
8
H x 4
1
/
2
W x 2
7
/
16
D
Dimensions Model 24A06. . . . . . . . . . . . . 3
13
/
16
H x 4
13
/
16
W x 2
1
/
8
D
Dimensions Model 24A07. . . . . . . . . . . . . 1
7
/
8
H x 4
9
/
16
W x 1
29
/
32
D
Single Level Temp
Switch Action . . . . . . . . . . . . . . . . . . . . . . SPST normally open
Average Time Delay . . . . . . . . . . . . . . . . . 45 seconds
Lead length. . . . . . . . . . . . . . . . . . . . . . . . 18 inches
Ambient temperature range . . . . . . . . . . . –20 to +140°F
Dual Level Temp
Switch Action . . . . . . . . . . . . . . . . . . . . . . Two independent: SPST normally open
Average Time Delay . . . . . . . . . . . . . . . . . 45 seconds
Lead length. . . . . . . . . . . . . . . . . . . . . . . . 18 inches
Ambient temperature range . . . . . . . . . . . –20 to +120°F
Agency . . . . . . . . . . . . . . . . . . . . . . . . . . . U.L. listed and C.S.A. certied. Design
complies with U.L. 873 T.I.R.E. standard
(Temperature Indicating & Regulating Equipment)
FEATURES
Level-Temp allows low voltage 2-wire thermostat to control line voltage loads such
as baseboard heaters.
Conduit hub or screw mounting.
Ideal for all types of electrical heat.
Non-critical mounting angle. Universal break-off mounting tabs.
Dual Level-Temp capable of controlling two separate loads.
Model Input Thermostat A.C. Resistive A.C. Motor Rating (Inductive)
Number Voltage/Frequency Current (Non-inductive) Full Load Locked Rotor
24A01G-3 240 VAC/60 Hz 0.2A 25A, 6000W, 240v 12A, 240v 72A, 240v
24A01Z-10 347 VAC/60 Hz 0.2A 17A, 5900W, 347v
24A05A-1 120 VAC/60 Hz 0.2A 25A, 3000W, 120v 16A, 120v 96A, 120v
24A05E-1 208 VAC/60 Hz 0.2A 22A, 5200W, 208v 12A, 208v 72A, 208v
24A05Z-1 277 VAC/60 Hz 0.2A 22A, 6000W, 277v
24A07E-1 208 VAC/60 Hz 0.2A 25A, 5200W, 208v 12A, 208v 72A, 208v
24A07G-1 240 VAC/60 Hz 0.2A 25A, 6000W, 240v 12A, 240v 72A, 240v
Same as 24A05E-1, except without enclosure (U.L. recognized only)
Same as 24A01G-3, except without enclosure (U.L. recognized only)
24A01G-3
SINGLE LEVEL TEMPS – Normally Open
Model Input Thermostat A.C. Resistive A.C. Motor Rating (Inductive)
Number Voltage/Frequency Current (Non-inductive) Full Load Locked Rotor
24A06G-1 240 VAC/60 Hz 0.2A per switch 25A, 6000W, 240v 12A, 240v 72A, 240v
DUAL LEVEL TEMPS – Controls Two Independent Loads – Normally Open
Electrical ratings apply to each switch load
NOTE: Delay approximately 30 seconds opening and 60 seconds closing
REPLACES HONEYWELL R841 SERIES
24A06G-1
Using Two-wire Heating Thermostat to
Operate Two Separate Heating Loads
ELECTRIC HEAT
PRODUCTS
TECHNICAL HELP
Wiring and Dimension Drawing, 24A01/24A05 . . . . page 286
MAKE L1 “HOT”
ON 120V MODELS
NOTE
Use thermostat with a .4A
fixed heater, or set adjustable
heater in thermostat at .4 A.
Indicates Canadian Model Number: call 1-800-305-6953 to order
?

Summary of content (1 pages)