Installation instructions

FAILURE TO READ AND FOLLOW ALL INSTRUCTIONS CAREFULLY
BEFORE INSTALLING OR OPERATING THIS CONTROL COULD CAUSE
PERSONAL INJURY AND/OR PROPERTY DAMAGE.
The 36C03 and 36C10 series valves are designed
to meet requirements for use on standing con-
tinuous pilot systems. 36C03 combination models
include a pressure regulator, 100% shut-o auto-
matic pilot, and main operator. 36C10 models do
not have a pressure regulator.
36C Inst
Voltage
# of
Stages
Open
Characteristics
Standing
Pilot
Intermittent Pilot
Proven Pilot
HSI DSI
36C03/36C10 24V 1 Fast Yes No No No
36C03U 750mV 1 Fast Yes No No No
36C03A 120V 1 Fast Yes No No No
PRESSURE REGULATOR ADJUSTMENT RANGE
EXCLUDING 36C10
Gas Type
Single Stage
Natural Gas 2.5–5.0
LP Gas 7.5–12.0
SPECIFICATIONS
DESCRIPTION
INSTALLATION INSTRUCTIONS
36C03, 36C03A, 36C03U & 36C10
Standing/Continuous Pilot Combination Gas Valve
OFF
PILOT
ON
ECO
Terminals
OFF
PILOT
ON
Pilot Gas Outlet:
Located at outlet end of the valve
Type of Gas: Suitable for all domestic heating
gases
Ambient Temperature: -40º to 175ºF
Pressure Rating: 14" W.C. (1/2 PSI) Max
Voltage/Current: 36C03U – 750mV
36C03/36C10 – 24V/0.23A
36C03A – 120V/0.035A
CONTENTS
Description ........................................................................... 1
Specications ....................................................................... 1
Precautions ........................................................................... 2
Installation ............................................................................ 3
System Wiring
Adjustment .......................................................................... 5
Pressure Regulator Adjustment
Lighting Instructions ............................................................ 6
Contents French ........................................................................ 9
Contents Spanish.....................................................................17
PIPE SIZES/CAPACITIES
Pipe Size
(inches)
Capacity (BTU/hr) at
1" pressure drop across valve
Range of Regulation
Excluding 36C10 Non-Regulated
Nat. Gas
(1000 BTU/cu. ft., 64
Sp. Gr.)
LP Gas
(2500 BTU/cu. ft.,
1.53 Sp. Gr.)
AGA Std. Nat. Gas
0.64 Sp. Gr.
(1,000 BTU/cu. ft.)
LP Gas
1.53 Sp. Gr.
(2,500 BTU/cu. ft.)
1/2" x 3/8"
100,000 162,000 15,000 - 100,000 15,000 - 162,000
1/2" x 1/2"
230,000 372,600 30,000 - 290,000 30,000 - 469,000
1/2" x 3/4"
230,000 372,600 30,000 - 290,000 30,000 - 469,000
3/4" x 3/4"
280,000 453,600 50,000 - 400,000 50,000 - 648,000
Parts and Accessories:
Conversion Kit
• F92-0659 Nat. to LP Gas (7.5" to 12.0" W.C.)
• F92-0737 Nat. to LP Gas (Non-regulated)
• F69-0727 1/4" brass compression tting for pilot
line connection
Thermocouple (24V & 120V types):
Use W-R Type H06
Pilot Generator (.750 volt types):
Use W-R Type G01A-32
www.white-rodgers.com
www.emersonclimate.com
PART NO. 37-7349B
Replaces 37-7349A