Install Instructions

Pilot Gas Outlet:
Located at outlet end of the valve
Type of Gas
Suitable for all domestic heating gases
Pressure Rating:
1
2 lb. per sq. in.
Pressure Regulator Adjust Range (Typical, See
Control Label):
Natural Gas: 2.5 to 5.0" W.C.
LP Gas: 7.5 to 12" W.C.
Ambient Temperature: -40° to 175°F
Thermocouple:
(24V types): Use W-R Type HO6
Pilot Generator (.750 volt types):
Use W-R Type G01A-32
Mounting: Any position except upside-down
PIPE SIZES/CAPACITIES
Pipe Size
(inches)
Capacity (BTU/hr) at
1” pressure drop across valve
1
2
” x
3
8
1
2
” x
1
2
1
2
” x
3
4
3
4
” x
3
4
100,000
230,000
230,000
280,000
162,000
372,600
372,600
453,600
Nat. Gas
(1000 BTU/cu. ft.,
64 Sp. Gr.)
LP Gas
(2500 BTU/cu. ft.,
1.53 Sp. Gr.)
INLET BOSS
UP OR DOWN
UPRIGHT
LEFT OR RIGHT
Upright, 90° from upright or vertical
NOTE: Control shown may not be identical
to replacement control.
ON
OFF
WHITE-RODGERS
EMERSON ELECTRIC CO.
9797 REAVIS ROAD
ST. LOUIS, MISSOURI 63123-5398
www.white-rodgers.com
Printed in U.S.A.
PART NO. 37-6264A
0124
INSTALLATION INSTRUCTIONS
WHITE-RODGERS
FAILURE TO READ AND FOLLOW ALL INSTRUCTIONS CAREFULLY BEFORE
INSTALLING OR OPERATING THIS CONTROL COULD CAUSE PERSONAL INJURY
AND/OR PROPERTY DAMAGE.
The 36C03 complete gas controls combine into a single
compact package the functions of 3-position gas cock,
pressure regulator, 100% shut-off automatic pilot, and
main operator. Separate models are available for use on
24 VAC and .750 VDC systems. These controls can be
mounted in any orientation except upside down.
MODELS AVAILABLE
Model No. Voltage
36C03
36C03U
Current
.23 Amp
DC
24 volts
.750 volts
Gas
Nat.
Nat.
OFF
PILOT
ON
ECO
Terminals
OFF
PILOT
ON
Operator: Save these instructions for future use!
DESCRIPTION
SPECIFICATIONS
36C03(U)-333 and -433
Universal Combination Gas Valves
(24 Volt and .750 Volt Models)