Brochure
www.white-rodgers.com
61
FURNACE
36C CYCLE PILOT GAS VALVES
With Redundant Pilot Solenoid Main Gas Regulator, Integral Gas
Pressure Switch and Electrical Connection on the Gas Valve for Mer-
cury Flame Sensor Connection
SPECIFICATIONS
Electrical Rating . . . . . . . . . . . . . . . . . . . . 0.6 amps
End to End Dimensions . . . . . . . . . . . . . . 3
15
/
16
”
Ambient Operating Range . . . . . . . . . . . . –40 to +175°F (–40 to 79°C)
Maximum Pressure Rating . . . . . . . . . . . .
1
/
2
PSI (14.0” W.C.)
Agency . . . . . . . . . . . . . . . . . . . . . . . . . . . A.G.A. and C.G.A. design certied
LP Internal
Regulator Conversion Reducer Inlet Wiring
Model Coil Gas Pipe Opening Regulator Adjustment Convertible Kit Line Flow Bushing Pressure Side See
Number Voltage Type Size Characteristic Setting Range Nat./LP Included Interrupter Direction Kit Tap Taps Figure ➀
36C84-912 24 VAC Natural
3
/
4
x
3
/
4
Fast Open 3.5” 2.5”–5.0” Yes Yes No Str. Thru Yes Yes No 7
36C84-913 24 VAC Natural
3
/
4
x
3
/
4
Fast Open 3.5” 2.5”–5.0” Yes Yes No Str. Thru Yes Yes No 12
36C84-921 24 VAC Natural
3
/
4
x
3
/
4
Fast Open 3.5” 2.5”–5.0” Yes Yes No Str. Thru Yes Yes No 7
36C84-923 24 VAC Natural
3
/
4
x
3
/
4
Fast Open 3.5” 2.5”–5.0” No No No Str. Thru No Yes No 14
36C84-926 24 VAC Natural
3
/
4
x
3
/
4
Fast Open 3.5” 2.5”–5.0” No No No Str. Thru Yes No No 4
36C84-945 24 VAC Natural
3
/
4
x
3
/
4
Fast Open 3.5” 2.5”–5.0” Yes Yes No Str. Thru Yes Yes No 8
36C87-944 24 VAC Natural
3
/
4
x
3
/
4
Step Open 1.0 1.0”/3.5” 2.5”–5.0” No No No Str. Thru Yes No No 11
36C94-906 24 VAC Natural
3
/
4
x
3
/
4
Slow Open 3.5” 2.5”–5.0” No No No Str. Thru Yes No No 7
36C94-907 24 VAC Natural
3
/
4
x
3
/
4
Slow Open 3.5” 2.5”–5.0” Yes Yes No Str. Thru Yes No No 4
36C
GAS VALVES
PARTS AND ACCESSORIES See end of this section for parts and accessories
36C84-912
➀ Wiring diagrams – see pages 250-253
NOTE: -9XX series replaces -4XX series. Knob replaced with an ON-OFF switch.
GAS BURNER
CONTROLS
TECHNICAL HELP
Wiring Diagrams. . . . . . . . . . . . . . . . . . . . . . See pages 250-253
AGA STD. NAT GAS LP GAS AGA STD. NAT GAS LP GAS
Pipe Size 1000 BTU/CU. FT. 2500 BTU/CU. FT. 1000 BTU/CU. FT. 2500 BTU/CU. FT.
1/2 X 3/8 100,000 162,000 15,000-100,000 15,000-162,000
1/2 X 1/2 230,000 372,600 30,000-290,000 30,000-469,000
1/2 X 3/4 230,000 372,600 30,000-290,000 30,000-469,000
3/4 X 3/4 280,000 453,600 50,000-400,000 50,000-648,000
1” Pressure Drop Capacity Rated Range of Regulation
BTU/HR BTU/HR
?
NEW!
NEW!
NEW!
NEW!
NEW!
NEW!
NEW!
NEW!
NEW!