Install Instructions

50I56D-905
Intelligent Gas Valve Retrot Kit For
ICP & Lennox Brand Systems
INSTALLATION INSTRUCTIONS
PARTS INCLUDED
50I56-905 120V HSI IP Furnace Control Board
1 - Main CONTROL Harness (0115-0339)
1 - Gas VALVE Harness (0115-0336)
1 - Ignitor/Inducer C Harness (0115-0256)
1 - 791Q-905KT1 120V Ignitor + Flame Sensor Kit
for Pilot Assembly
1 - 36G33-905 IP Gas Valve
The 50I56D-905 Retrot Kit is an aftermarket service solution for popular ICP and Lennox brand furnaces using SV9500,
SV9501 and SV9502 Intelligent Valves and Fan Timer Control boards. Upgrades system from 24V to 120V hot surface pilot
ignition and utilizes reliable standard IP gas valve. For single stage furnaces with PSC inducer and blower motors.
DESCRIPTION
SPECIFICATIONS
Failure to comply with the following warnings could result
in personal injury or property damage.
Installation should be done by a qualied heating and
air conditioning contractor or licensed electrician.
All wiring must conform to local and national electrical
codes and ordinances.
Following installation or replacement, follow
manufacturer’s recommended installation/service
instructions to ensure proper operation.
FIRE HAZARD
Do not exceed the specied voltage.
Protect control from direct contact with water (dripping,
spraying, rain, etc.).
If the control has been in direct contact with water,
replace the control.
Label all wires before disconnection when servicing
controls. Wiring errors can cause improper and
dangerous operation.
Route and secure wiring away from ame.
SHOCK HAZARD
Disconnect electric power before servicing.
Ensure proper earth grounding of appliance.
Ensure proper connection of line neutral and line hot
wires.
EXPLOSION HAZARD
Shut off main gas to appliance until installation is
complete.
WARNING
!
FAILURE TO READ AND FOLLOW ALL INSTRUCTIONS CAREFULLY BEFORE
INSTALLING OR OPERATING THIS CONTROL COULD CAUSE PERSONAL
INJURY AND/OR PROPERTY DAMAGE.
emerson.com/white-rodgers
PART NO. 37-7838001
2105
4 - 1” Sheet Metal Mounting Screws
4 - Wire Ties
2 - 1/4” Female Crimp-on Spades
2 - 7/8” Sheet Metal Wire Grommets
Unit Retrot Label
Installation Instructions
Troubleshooting Label on Control Cover
ELECTRICAL RATINGS:
Input Low Voltage: 25 VAC, 60 Hz
Input Line Voltage: 120 VAC, 60 Hz
Max. Input Current: .45A @ 25 VAC
Flame Current Requirements:
Minimum current to insure ame detection: 0.25 µa DC*
Maximum current for non-detection: 0.1 µa DC
Maximum allowable leakage resistance: 100 M ohms
*Measuring with a DC voltmeter (1VDC = µA)
Relay Contact Ratings:
Inducer Output: 2.2 FLA @ 120 VAC
3.5 LRA
Blower Output: 14.5 FLA @ 120 VAC
25 LRA
Gas Valve Output: 1.5A @ 25 VAC 0.6 pf
Ignitor Output: 6.0A @ 120 VAC (resistive)
Hum and EAC Load: 1.0A @ 120 VAC
OPERATING TEMPERATURE RANGE:
-40° to 176°F (-40° to 80°C)
HUMIDITY RANGE:
5 to 95% relative humidity (non-condensing
GASES APPROVED: Natural, Manufactured, Mixed,
Liquid Petroleum, and LP Gas Air Mixtures.