Brochure

www.white-rodgers.com
110
RELAYS and
TRANSFORMERS
3 POLE DEFINITE PURPOSE
CONTACTORS (25A THRU 40A)
90-160 THRU 90-172 WR/RBM TYPE 154
Designed for Central Air Conditioning and Heating Equipment
SPECIFICATIONS
Insulating Material . . . . . . . . . . . . . . . . . . Contact block and carrier are high quality
electrical-grade thermosetting resin
Temperature Range . . . . . . . . . . . . . . . . . –40°F to 150°F
Mechanical Life. . . . . . . . . . . . . . . . . . . . . Conforms to UL and ARI specications
Electrical Life . . . . . . . . . . . . . . . . . . . . . . Conforms to UL and ARI specications
Weight (approximate) . . . . . . . . . . . . . . . . 16 oz.
Agency . . . . . . . . . . . . . . . . . . . . . . . . . . . U.L. le number E75492
C.S.A. le number LR49598
Coils Frequency . . . . . . . . . . . . . . . . . . . . 50/60 Hz
Coil Insulation. . . . . . . . . . . . . . . . . . . . . . Class B (130°C)
24 through 208/240 Volts AC
Termination. . . . . . . . . . . . . . . . . . . . . . . . Pressure connector and Double
1
/
4
Q.C.
Operate. . . . . . . . . . . . . . . . . . . . . . . . . . . 85% of nominal coil voltage;
110% maximum safe operate
Duty Cycle . . . . . . . . . . . . . . . . . . . . . . . . Continuous
Model Number Coil Voltage AC Res DC Current Nominal Max. Inrush
25 Amp 30 Amp 40 Amp (60 Hz) OHMS MA VA VA
90-160 90-163 90-170 24 7.2 187 4.5 52
90-161 90-164 90-171 120 180 37 4.5 52
90-162 90-165 90-172 208/240 720 19 4.5 52
Approximate Overall Dimensions
3
3
/
4
x 2
3
/
8
x 3
COIL DATA – 25, 30 and 40 Amp, 600 Volt Three Pole Normally Open (3 P.N.O.)
Type Voltage 277 VAC 480 VAC 600 VAC
90-160 Full Load 25 A. 25 A. 25 A.
thru Lock Rotor 150 A. 125 A. 100 A.
90-162 Resistive 40 A. 40 A. 40 A.
90-163 Full Load 30 A. 30 A. 30 A.
thru Lock Rotor 180 A. 150 A. 120 A.
90-165 Resistive 50 A. 50 A. 50 A.
CONTACT RATINGS – 25 and 30 Amp, 600 Volt Three Pole Normally Open (3 P.N.O.)
FEATURES
Any position mounting.
Interchangeable mounting plate.
Low wattage coil.
Double break contacts ensure positive make and break.
40 Amp with Cover
Pressure Connectors line and load sides for #14
thru #4 wire.
1
/
4
Double Quick Connect auxiliary
and coil terminals.
Type Voltage 277 VAC 480 VAC 600 VAC
Full Load 40 A. 40 A. 40 A.
90-170 thru 90-172 Lock Rotor 240 A. 200 A. 160 A.
Resistive 50 A. 50 A. 50 A.
CONTACT RATINGS – 40 Amp, 600 Volt Three Pole Normally Open (3 P.N.O.)
2.983
3.390
3.2503.750
.203
.250
2.000
3.125
.203
2.414
90-160 thru 90-172