Installation Instructions
CMM-3U & CMM-3UK Zoning Panel
Installation & Operating Instructions
Form 37-6863A
1 of 6
© 2004 White-Rodgers by Permission
Product Data
• Single Stage gas and electric systems
• Multi Stage (2H/1C) gas and electric systems
• Heat Pump (3H/1C)
• 2-3 zones
• 5-Year Warranty
Specifications
• Construction: ABS Plastic
• Dimensions: 7 ⅝” x 7 ¼” x 1 ⅜”
• Voltage: 24 Volts AC, 50/60 Hz
• Operating Temperature: 0°- 120°
• Shipping/Storage Temperature: -20°- 140°
• Humidity Range: 5% - 95% Non-Condensing
Kit Contents (CMM-3UK)
• CMM-3U
• CLAS (leaving air sensor)
• COAS (outdoor air sensor for heat pumps)
• 24V Transformer
Recommended Dampers
• CRDS – round damper (24V)
• CZDS – rectangular, side mount motor (24V)
• CZDB – rectangular, bottom mount motor (24V)
• CSPRD – static pressure relief dampers
24V dampers are power close, spring open and are
convertible to power open, spring close
Recommended Thermostats
• 1F78-151 (5+2 programming)
• 1F78-144 (non-programmable)
• 1F85-0471 (5+1+1,5+2,0 programming)
• 1F80-0471 (5+1+1,5+2,0 programming)
• 1F97-1277 (7, 5+1+1,0 programming)
• 1F95-1277 (7, 5+1+1,0 programming)
• 1F85RF-275 (5+1+1,5+2,0 programming) (wireless)
To prevent electrical shock and/or
equipment damage, disconnect electric
power to system at main fuse or circuit
breaker box until installation is com
p
lete
SAVE THESE INSTRUCTIONS FOR
FUTURE USE!
Failure to read and follow all instructions
carefully before installing or operating
this control could cause personal injury
and/or
p
ro
p
ert
y
dama
g
e.
Terminal
Destination
Description
W2/E….…… 2nd Stage Heat (Emergency heat for Heat Pumps)
G…………… Fan Relay
Y…………… Compressor
R…………… Power for Heating/Cooling
W/OB……… Heat Relay/Changeover Valve for Heat Pump
C…………… Common Wire