White-Rodgers P.O. Box 6977 Br 9797 Reviser Road St. Louis, Missouri 63123 CS-1000 ELECTRONIC AIR CLEANER A a MODEL NO. 10C26E-41000 OPERATION AND INSTALLATION MANUAL «, Printed in U.S.A. Form No.
TABLE OF CONTENTS Subject Page Subject Page 1. INTRODUCTION IV. MAINTENANCE/WASHING A. How Your Air Cleaner Works. . 2 A. Washing Cell . 8 B. Specifications +3 B. lionizing Wire Replacement . 8 GC. Efficiency . .3 Co 0Z0N. vertices 8 D. Warnings. ELECTRICAL i en iF ORATION 3 A. Electrical Troubles and Corrections B. Application ‘a B. Power Supply Replacement GC. Energy Saving . +3 ELECTRICAL 9 D. Sizing . 8 11. INSTALLATION VIL PARTS LIST... A. .5 E. Ordering Information . B. Ceiling Mounting . 8 C.
B. SPECIFICATIONS The Air Cleaner takes its energy saving power requirements (approx. 250 watts) from standard electrical wiring systems. No special provisions are required. Local residential and commercial wiring codes apply. CURRENT AND POWER CONSUMPTION VOLTAGE: 120AC-80HZ AMPS: Hi-Speed 2.5 WATTS: Hi-Speed 240 FAN SPEED: Variable 200 to 1000 CFM D.C. OUTPUT VOLTAGE + OUTPUT TO GROUND: 6400 VDC £ 250V (Cell Connected) WEIGHT: 66 lbs. SHIPPING WEIGHT: 76 Ibs. (37 kg) C.
SIZING CHART FOR YOUR AIR CLEANER CAFETERIAS © powwowing [LUNCHEONETTES, 2 centers LoL = fuss 5 10-4 PF F < PLACES OF | ASSEMBLY | Lr stores —t s-Orifices I UNITS REQUIRED SeTelsTaTleTxT=1+1 53 [501 wars toa] 1810 fs} Capacity is gab t } epee he Lo Seb df 2150 tat AREA IN SQUARE FEET [SQUARE METERS IN BRACKETS] T 60 fas] as [EC] 4300 Teo £400} The number of air changes per hour determines the amount of air cleaning obtained.
Il. INSTALLATION A. PLACEMENT The installer must be qualified to make approved electrical connections and a safe ceiling installation with attention to the best placement as shown in the following drawings. The electronic Air Cleaner should be mounted on the ceiling near the center of the room, Air is drawn into the bottom of the air cleaner and discharged in four (4) directions. Divide larger corms into sections and use a unit in the center of each section (see Fig. 3).
IV. MAINTENANCE/WASHING A. WASHING CELL When to Wash: Periodically the dirt collected by your unit must be removed. The frequency of washing will depend on the amount of dirt present in the air in your locality. Frequent washings are in no way harmful to your unit, but prolonged use without cleaning will decrease its dirt collecting ability. The washing frequency best suited for your unit can be determined by examining the dirt collecting components at three week intervals.
An ionizing-collecting cell that has been damaged, where in the designed spacing between electrically charged and ground components has been decreased, may also produce an abnormal amount of ozone. CHECK LIST FOR ABOVE: Check for: 1. Damaged (bent) plates Straighten or replace. 2. Loose ionizing wires Repair or replace. 3. Dirty Cell Clean. V.
QUICK REFERENCE TROUBLE CHART CONDITION oR TROUBLE | PROBABLE SYMPTOM DESCRIPTION | LOCATION | PROBABILITY POSSIBLE CAUSE CORRECTION Broken lan Wire Remove & Replace Excessive Dirt Wash Indicating Short Cell Good Object Between Plates Remove Light Circuit Damaged (Bent) Plates Straighten or Replace Out Damaged {Bent} Ionizer Straighten or Replace Broken Insulator Replace Indicating Light Short Power Fair Defective Replace fut Circuit Supply Power Supply indicating Light Qut Light But indicating | Remote Def
TN VI. ELECTRICAL TROUBLE SHOOTING CAUTION FOLLOWING SERVICE PROCEDURE EXPOSES LIVE VOLTAGE PARTS AND SHOULD BE CONDUCTED BY QUALIFIED PERSONNEL ONLY! SUPPLY CONNECTIONS SHOULD BE DISCONNECTED BEFORE PROCEEDING. 1. There are two areas in which the majority of service problems originate. A. The lionizing-Collecting Cell B. The Power Supply The cell, which is removed from the unit periodically to wash away the collected dirt, is more susceptible to physical damage through handling than the power supply.
PARTS LIST: MODEL 10C26E-41000 ELECTRIC AIR CLEANER Key Part No. Description F825-0357. 20x20 Filterer F811-0414 Collecting Cell (2 Re) F858-0888 Power Supply F876-019¢ Interlock Safety Switch FB76-0203 High-Low Switch (Variable) F849-0060 Motor _1FB48-0315 Fan Blade F825-0460 Charcoal Filter Fg844-0143 Indicator Light F839-0018 Knob 23] ole| jo ols ooo | + § F843-0500 ionizing Wire ORDERING INFORMATION When purchasing equipment or replacement pairs from your Distributor use the Paris List.
WARRANTY TO. CONSUMER PURCHASER EMERSON Electronic Air Cleaners LIMITED WARRANTY “ This type White/Rodgers electronic air cleaner is warranted to the consumer against defects in materials and workmanship for 12 months from date of installation. The electronic air cleaner must be installed by a competent heating and/or air-conditioning contractor in accordance with White/Rodgers installation. instructions, operated within the unit’s listed capacity, and not moved frog the original installation site.