user manual

36C94-303
Delay-Opening Combination Gas Valve
PART NO. 37-7086B
Replaces 37-7086A
1024
INSTALLATION INSTRUCTIONS
FAILURE TO READ AND FOLLOW ALL INSTRUCTIONS CAREFULLY BEFORE
INSTALLING OR OPERATING THIS CONTROL COULD CAUSE PERSONAL
INJURY AND/OR PROPERTY DAMAGE.
DESCRIPTION
SPECIFICATIONS
PRECAUTIONS
36C94-303 is a direct replacement for 36C94-302, 36E93-301,
36E93-302, 36E93-303 and 36E93-304. The 36C94-303 com-
bination gas valve is designed for intermittent ignition system
applications. The valve is equipped with a redundant solenoid
Type of Gas: Natural gas
LP gas (use conversion kit)
Pressure Regulator Adjustment Range:
Nat. Gas – 2.5 to 5.0" W.C.
L.P. Gas – 7.0 to 12" W.C.
Pipe Size:
Inlet – 1/2" NPT
Outlet – 3/4" NPT
Capacity @ 1" pressure drop across valve:
230,000 BTU/HR of 0.64 SP GR.
1,000 BTU/CU. FT gas
Ambient Temperature: –40 to +175°F (–40 to 79°C)
Pressure Rating: 14" W.C. (1/2 PSI) max.
Electrical Rating: 24 VAC, 60 Hz, 0.6 A
Parts and Accessories:
F92-0656 - LP to Natural Gas Conversion Kit for use on
Single Stage 36C, D, E, F, G, H, J valves. Regulation range
2.5" to 5.0" W.C.
F92-0659 - Natural to Regulated LP Gas conversion Kit for
use on Single Stage 36C, D, E, F, G, H, J valves. Regulation
range 7.0" to 12.0" W.C.
www.white-rodgers.com
www.emersonclimate.com
valve that controls gas flow to the pilot and main burners, a main
valve that controls gas flow to the main burner, a pressure regula-
tor to maintain a constant outlet pressure, integral gas pressure
switch and a two position on/off switch for electrical shutoff.
WARNING
!
If you do not follow these instructions exactly, a fire or explosion
may
result causing property damage, personal injury or loss of life.
1. Failure to turn off electric or main gas supply to heating system could cause personal injury and/or property
damage by shock, gas suffocation, fire, and/or explosion.
2. Do not use this control on circuits exceeding specified voltage. Higher voltage will damage the control and
may cause shock or fire hazard.
3. NEVER USE FLAME OR ANY KIND OF SPARK TO CHECK FOR GAS LEAKS–COULD CAUSE FIRE AND/OR
EXPLOSION.
4. Do not use a control set for natural gas with LP gas, or a control set for LP gas with natural gas. Personal
injury and/or property damage, gas suffocation, fire, and/or explosion may result.
DO NOT BEGIN INSTALLATION UNTIL YOU READ THE FOLLOWING PRECAUTIONS.