Specification Sheet

www.white-rodgers.com
134
HYDRONIC
ZONE VALVES
HYDRONIC
CONTROLS
HYDRONIC ZONE CONTROLS
Two Types of Valves, 2-Wire or 3-Wire, for Zoning Hydronic
Systems up to 50 PSI
FEATURES
Quiet operation.
Valve stem made of stainless steel.
Automatic recycling manual operator shows valve position at all times.
Built-in auxiliary contacts to control burner or circulator relay.
Motor can be removed from valve assembly without draining system.
SPECIFICATIONS
Electric rating of auxiliary switch. . . . . . . . 2.0A at 24VAC
Four zone valves operate with one 40 VA transformer
1311-102
Maximum Maximum Maximum Flow Friction Loss
Model 24VAC Thermostat Time Differential Water System Capacity Equivalents
Number Tubing Size (I.D.) Circuit Rating Cycle Across Valve Temp. Pressure Cv Ft. of Tubing
1311-102
3
/4 0.4A Open: 45 seconds 15 PSI 240°F 50 PSI 23.5 2
1
/2
Close: 45 seconds (116°C)
1311-103 1 0.4A Open: 45 seconds 15 PSI 240°F 50 PSI 37.0 3.5
Close: 45 seconds (116°C)
1311-104 1
1
/4 0.4A Open: 45 seconds 15 PSI 240°F 50 PSI 42.2 6.5
Close: 45 seconds (116°C)
PARTS AND ACCESSORIES See end of this section for additional parts and accessories
F19-0097 — Motor assembly for 3-wire zone valves
F19-0104 — Motor assembly for 2-wire zone valves
F84-0433 — Valve assembly for
3
/
4
(both series)
F84-0434 — Valve assembly for 1 (both series)
F84-0435 — Valve assembly for 1
1
/
4
(both series)
F92-0227 — Water seal kits for
3
/
4
(both series)
F92-0228 — Water seal kits for 1 (both series)
F92-0229 — Water seal kits for 1
1
/
4
(both series)
➀Valve current is 0.4A only during opening or closing. For proper anticipation, select thermostat designed for use with a 3-wire zone valve.
Valve current is 0.52A when opening but 0.2A when fully open: therefore set anticipator for 0.2A. GPM @ 1 PSI drop.
DO NOT CHANGE VALVE ASSEMBLY WITHOUT DRAINING BOILER OR WHILE BOILER WATER IS
HOT. FAILURE TO RELIEVE WATER PRESSURE OR WAIT UNTIL WATER COOLS COULD RESULT IN
SCALDING INJURIES
VALVE DIMENSIONS (inches)
SIZE A B C D E
3
/4 1
3
/4 6
1
/2 2
7
/8 4
11
/16 5
5
/8
1 1
15
/16 6
3
/4 3
1
/8 4
13
/16 5
7
/8
1
1
/4 2
1
/8 7
1
/8 3
11
/16 5 6
1
/4
CONTRACTOR TIP: FOR HEAT/COOL APPLICATIONS, SEE 752-1 CONTROL ON PAGE 137.
3-WIRE, 24V VALVES WITH SCREW TERMINAL WIRING PANEL AND AUXILIARY SWITCH (SEE TABLE AT BOTTOM FOR COMPATIBLE THERMOSTATS)
Maximum Maximum Maximum Flow Friction Loss
Model 24VAC Thermostat Time Differential Water System Capacity Equivalents
Number Tubing Size (I.D.) Circuit Rating Cycle Across Valve Temp. Pressure Cv Ft. of Tubing
1361-102
3
/4 0.2A Open: 45 seconds 15 PSI 240°F 50 PSI 23.5 2
1
/2
Close: 60 seconds (116°C)
1361-103 1 0.2A Open: 45 seconds 15 PSI 240°F 50 PSI 37.0 3.5
Close: 60 seconds (116°C)
1361-104 1
1
/4 0.2A Open: 45 seconds 15 PSI 240°F 50 PSI 42.2 6.5
Close: 60 seconds (116°C)
2-WIRE, 24V VALVES WITH SCREW TERMINAL WIRING PANEL AND AUXILIARY SWITCH
TECHNICAL HELP
Zone Valve Troubleshooting . . . . . . . . . . . See pages 298-299
1311 COMPATIBLE THERMOSTATS TABLE
Model Number Programming Options Contacts Profile Terminals
1E35-910 Non-Programmable Sealed Mercury Cell Vertical 4, 5, 6
1F35-910 Non-Programmable Sealed Mercury Cell Horizontal 4, R5, Y6
1F90-371 5+1+1, 5+2 Electronic Horizontal RC, RH, W, Y, G, MV, O, B, +, S, -, 6
1F96-344 Non-Programmable Electronic Horizontal RC, RH, W, Y, G, MV, O, B, +, S, -, 6
1F97-371 7-Day Electronic Horizontal RC, RH, W, Y, G, MV, O, B, +, S, -, 6
1F95-1277 Touch Screen 7-Day, 5+1+1, or Non-Programmable Electronic Horizontal RC, RH, C, W/E, W2, Y, Y2, G, O, B, 6, L, +, S, -
1F97-1277 Touch Screen 7-Day, 5+1+1, or Non-Programmable Electronic Horizontal RC, RH, C, W, Y, G, O, B, W/E, L, 6, +, S, -
1F97-391 7-Day Electronic Horizontal RC, RH, W, Y, G, 6, HM1, HM2, S1, S2, S3
1F80-0471 5+1+1, 5+2, or Non-Programmable Electronic Horizontal RC, RH, C, W, Y, G, O/B
1F86-0471 Non-Programmable Electronic Horizontal RC, RH, C, W, Y, O/B
?