Specification Sheet

www.white-rodgers.com
96
FURNACE
MODEL 24A34 ELECTRIC HEAT SEQUENCERS
Direct Replacement for Most Fan/Heat Sequencing Functions.
Terminal Markings are Equivalent to Competitive Types
FEATURES
Replaces Honeywell, MARS, TOD,
GEMLINE, Klixon (Texas Instruments).
24V input control.
Multi-poise mounting.
Resistive (Non-Inductive) Motor Ratings (Inductive)
VAC Watts Amps Full Load Locked Rotor Pilot Duty
120 3000 25.0 14.0A 72.0A 125 VA
240 6000 25.0 7.0A 42.0A 125 VA
480 6000 12.5 480 VA
ELECTRICAL RATINGS – SINGLE LOAD CONTACT RATINGS (ALL MODELS)
Any contacts (except M1 & M2) can be
used as auxiliary contacts.
Double quick-connect terminals for
combination loads.
SPECIFICATIONS
Ambient Temperature Rating . . . . . . . . . . –50 to +165°F
Agency . . . . . . . . . . . . . . . . . . . . . . . . . . . U.L. component recognized
Model Timings – ON Timings – OFF
Number Timings Switches M1-M2 M3-M4 M5-M6 M7-M8 M9-M10 M1-M2 M3-M4 M5-M6 M7-M8 M9-M10
24A34-1 1 1 1-20 40-110
24A34-2 1 1 30-90 1-30
24A34-3 1 2 1-20 1-20 40-110 40-110
24A34-4 1 2 30-90 30-90 1-30 1-30
24A34-5 2 3 1-110 1-110 1-110 1-110 1-110 1-110
24A34-6 2 4 1-110 1-110 1-110 1-110 1-110 1-110 1-110 1-110
24A34-14➀➁ 4 5 1-160 1-160 1-160 1-160 1-160 1-160 1-160 1-160 1-160 1-160
24A34-21 1 1 1-20 1-50
24A34-22 1 1 15-45 1-30
24A34-23 1 1 25-55 15-45
24A34-24 1 1 30-75 1-40
24A34-25 1 1 40-90 1-30
24A34-26 2 2 1-20 30-90 40-90 1-30
24A34-27 2 2 1-160 1-160 1-160 1-160
24A34-28 2 2 1-160 1-160 1-160 1-160
24A34-29 1 1 15-35 25-55
24A34-36 2 2 1-20 30-45 45-110 1-30
24A34-37 1 1 1-110 1-110
TABLE NOTES:
M1-M2 and M3-M4 are always rst switches
to turn ON and last to turn OFF. All other
switches are random ON and random OFF
24A34-14 Switch contacts designated
F
1
- F
2
instead of M
1
- M
2
24A34-28 is 2 pole double throw
These contacts switch simultaneously
NOTE: Underwriters Laboratories requires a
fan interlock circuit to insure the blower
remains operating whenever more than one
sequencer is used. The fan interlock should
be the M
1
/M
2
contacts of the second or third
sequencer.
All M
1
/M
2
contacts are wired to the blower mo-
tor so that any sequencer that is energized will
COMBINED LOAD RATING TABLE
(ALL MODELS)
30A @ 240 VAC – TOTAL,
23A Non-Inductive + 7 FLA/42 LRA Inductive,
ON Time: Elapsed time to make contacts after
heater is energized (min. to max.)
OFF Time: Elapsed time to break contacts after
heater is de-energized (min. to max.)
24A34-3
Model Timings
Number Timings Switches ON 1-3 OFF 1-3
24A34-15 1 1 1-60 75-95
24A34-15 HEAT PUMP CONTROL
FEATURES
Used in heat pump air handler applications.
Provides a delay off to the blower motor in cooling mode.
Single pole double throw.
Resistive (Non-Inductive) Motor Ratings (Inductive)
VAC Watts Amps Full Load Locked Rotor Pilot Duty
120 3000 25.0 14.0A 72.0A 125 VA
240 6000 25.0 7.0A 42.0A 125 VA
ELECTRICAL RATINGS – NORMALLY OPEN CONTACTS 1-3
Resistive (Non-Inductive)
VAC Watts Amps Pilot Duty
120 1200 10.0 125 VA
240 1200 5.0 125 VA
ELECTRICAL RATINGS – NORMALLY CLOSED CONTACTS 1-2
ELECTRIC HEAT
PRODUCTS
Indicates Canadian Model Number: call 1-800-305-6953 to order