Installation Manual

RecommendedOCPDsizepergrid:
Inverter 208 VAC 480 VAC
SE9KUS* 35A ---
SE10KUS* --- 15A
SE20KUS* --- 30A
* Youmayusealargersizethanrecommendedbutneverabove40A.
Default Trip Limits and Times According to IEEE1547
NOTE
The inverters are equipped with adjustable utility protective function set-points, and can be aggregated above 30kW on a single Point of
Common Connection. The default settings are in compliance with IEEE1547. Utility authorization is required to change these set-points.
Voltage Range (% of Base Voltage) Max. Clearing Time (Sec)
V < 50% 0.16
50 % < V < 88% 2.00
88% < V < 120 1.00
V > 120 % 0.16
Frequency Range (Hz) Max. Clearing Time (Sec)
> 60.5 0.16
< 59.3 (Hawaii 57) 0.16