6. Equipment Commissioning
66
WiBAS-Connect TS, Continued
Procedure for WiBAS-Connect TS with Parabolic Low Profile Antenna,
continued
Step
Action
5b
Perform fine alignment, as follows:
Use the spanner key to loosen the elevation adjustment bolts (E). Perform
elevation adjustment by holding tool’s handles firmly and slightly move the
antenna/radio combo (within the ±10
o
range around the elevation axis) until the
voltage readout reaches a desired level.
(E) = Elevation bolts x 2 (left and right).
The RSSI voltage (actually the voltmeter value) provides a direct
relationship with RSL.
For WiBAS-OSDR see
WiBAS-OSDR terminal station RSSI measurement
calculation formula on page 41,
For WiBAS-Connect see
WiBAS-Connect terminal station RSSI
measurement calculation formula on page 41).
6b Use the adjustable torque wrench for pre-tightening.
The final tightening torque
will be applied after alignment process completion.