Operating Instructions Temperature Indicating Controller, Model CF1M WIKA Operating Instructions CF1M WIKA Alexander Wiegand GmbH & Co. KG Alexander-Wiegand-Straße 30 63911 Klingenberg/Germany Phone (+49) 93 72/132-0 Fax (+49) 93 72/132-406 E-Mail info@wika.de www.wika.de V1.
Operating Instructions Temperature Indicating Controller CF1M To prevent accidents arising from the use of this controller, please ensure the operator using it receives this manual. Warning Turn the power supply to the instrument OFF before wiring or checking. Working or touching the terminal with the power switched ON may result in Electric Shock, which can cause severe injury or death. 1.
Operating Instructions Temperature Indicating Controller CF1M 2. Name and functions of the section (1) key (2) (3) (4) (5) key (6) MODE key (7) OUT/ 1 2 3 OFF key : Increases the numeric value. : Decreases the numeric value. : Selects the setting mode. : Turns the control output ON or OFF. 4 (1) PV indicator (2) SV indicator : The red LED lights up while Process variable is being indicated on the PV/SV display. : The red LED lights up while Setting value is being indicated on the PV/SV display.
Operating Instructions Temperature Indicating Controller CF1M 3.1 Operation flow chart Control output OFF function PV/SV display mode (Approx. 1s) [ ] Output manipulating value display (Approx. 3s) + [Main setting mode] Main setting 1 [ + [Sub setting mode] AT Perform/Cancel or Auto reset Perform [ ] Main setting 2 [ ] (Approx. 3s) [Auxiliary function setting mode 1] PV/SV display change / ] [ ] + + (Approx.
Operating Instructions Temperature Indicating Controller CF1M 3.2 Main setting mode Character Name, Description, Setting range Main setting 1 • Sets Main setting value 1 of the main control. • Main setting low limit value to Main setting high limit value Main setting 2 • Sets Main setting value 2 of the main control. • This setting item is available only when the option [SV2] is applied. • Main setting low limit value to Main setting high limit value 3.
Operating Instructions Temperature Indicating Controller CF1M Loop break alarm action time setting • Sets the time it takes to assess the Loop break alarm. • This setting item is available only when the “Loop break alarm” is selected in “Event output function selection”. • 0 to 200 minutes Loop break alarm action span setting • Sets the span to assess the Loop break alarm. • This setting item is available only when the “Loop break alarm” is selected in “Event output function selection”.
Operating Instructions Temperature Indicating Controller CF1M Sensor correction setting • Sets sensor correction value. • -100.0 to 100.0°C (°F) Instrument number setting • Sets the Instrument number individually to each instrument when communicating by connecting multiple instruments in serial communication. • This setting item is available only when the option [CR5] is applied. • 0 to 95 Transfer rate setting • Selects the communication transfer rate to meet the rate of the host computer.
Operating Instructions Temperature Indicating Controller CF1M Output ON/OFF action hysteresis setting • Sets the ON/OFF action hysteresis of control output. • This setting item is available only for the ON/OFF action. • 0.1 to 100.0°C Event output function selection • One of the functions is selectable from Temperature alarm, Loop break alarm or Heater burnout alarm. • Heater burnout alarm can be selected only when option [W1X] is applied.
Operating Instructions Temperature Indicating Controller CF1M Output Direct/Reverse change • Changes the output action Reverse (Heating) or Direct (Cooling). • Reverse (Heating) action: Direct (Cooling) action : Auto-tuning bias setting • Sets PID auto-tuning bias value. • 0 to 50°C (0 to 100°F) With decimal point, 0.0 to 50.0°C (0.0 to 100.0°F) Reverse (Heating) action 20°C (40°F) Sensor correction function Corrects the input value from the sensor.
Operating Instructions Temperature Indicating Controller CF1M 3.6 Control output OFF function Character Name, Descriptions Control output OFF function • This is the function to switch the control output OFF even if power is supplied to the instrument. The function is used when required to halt the control action or the CF1M is not used in multiple controllers. " is indicated on the PV/SV display. " • This function can be selected from any mode or any setting item by pressing the OUT/OFF key for approx.
Operating Instructions Temperature Indicating Controller CF1M (2) Self-diagnostic function The CPU is monitored by a watchdog timer, and when any abnormal status is found on the CPU, the controller is switched to warm-up status. (3) Automatic cold junction temperature compensation (thermocouple input type) Detects the temperature at the connection terminal between thermocouple and instrument, and always keeps it on the same status as when the reference junction is located at 0°C (32°F). 6.
Operating Instructions Temperature Indicating Controller CF1M 6.2 ON/OFF action drawing Action Heating (reverse) action Cooling (direct) action Hysteresis Hysteresis ON ON OFF OFF Control action Setting Relay contact output Non-contact voltage output 3 3 3 3 4 4 4 4 + 3 + 3 12Vdc • 03/2005 + 3 0Vdc 12Vdc 4 4 4 + 3 + 3 + 3 + 3 20mAdc 4 4mAdc 4 Lit Unlit part: Acts ON or OFF. V1.
Operating Instructions Temperature Indicating Controller CF1M 6.
Operating Instructions Temperature Indicating Controller CF1M 6.4 Heater burnout alarm drawing ON OFF 11 11 12 12 Setting Lit Small Load current Unlit Large 7. PID auto-tuning of the CF1M In order to decide each value of P, I, D and ARW automatically, this system forcibly fluctuates the object being controlled. h When the difference between setting value and processing temperature is large when the temperature rises. Fluctuation is given at the temperature 20°C (°F) lower than the setting value.
Operating Instructions Temperature Indicating Controller CF1M h When the difference between setting value and processing temperature is large when the temperature falls. Fluctuation is given at the temperature 20°C (°F) or higher than the setting value. Temperature 20 C ( F ) higher than the setting value Temperature 1 PID parameter measuring 2 PID parameter calculated point 4 3 Controlling action is performed with the parameters set by autotuning.
Operating Instructions Temperature Indicating Controller CF1M 45 +0.6 0 40 22.2 +0.3 0 8.3 Panel cutout drawing 60 [Fig. 8.3-1] 8.4 CT (current transformer) dimension drawing CTL-6-S (5A, 10A, 20A) CTL-12-S36-10L1 (50A) 8.5 Mounting Mounting panel thickness is from 1 to 10mm. Insert the CF1M from the front of the panel. Insert the mounting frame as shown in [Fig. 8.5-1] until the four tips of the frame touch the front panel. [Fig. 8.5-1] V1.
Operating Instructions Temperature Indicating Controller CF1M 9. Terminal arrangement Warning Turn the power supply to the instrument OFF before wiring or checking. Working or touching the terminal with the power switched ON may result in an Electric Shock which could cause severe injury or death.
Operating Instructions Temperature Indicating Controller CF1M Option: Heater burnout alarm output (1) This alarm is not available for detecting current under phase control. (2) Use the current transformer (CT) supplied and pass one lead wire of heater circuit into the hole of the CT. (3) When wiring, keep CT wire away from AC source and load wire to avoid external interference. 8 9 CT input terminal Power source CT [Fig. 7-2] Heater 8. Specifications 8.
Operating Instructions Temperature Indicating Controller CF1M Temperature alarm output The alarm action point is set by ± deviation to the main setting (except Process value alarm). [When the alarm action is set as energized] When the input exceeds the range, the output turns ON or OFF (in the case of High/Low limit range alarm). [When the alarm action is set as deenergized] The output acts conversely. • Setting accuracy Thermocouple : Within ±0.
Operating Instructions Temperature Indicating Controller CF1M Insulation resistance 10MΩ or greater at 500Vdc In the case of the above Circuit insulation configuration (*), because the communication and output terminals are not isolated from one another, the insulation resistance test must not be carried out. Dielectric strength Between input terminal and ground ---------------- 1.5kVac for 1 minute Between input terminal and power terminal ------ .1.
Operating Instructions Temperature Indicating Controller CF1M Heater burnout alarm [Option code: W1X] Watches the heater current with CT (current transformer), and detects the burnout. This option cannot be applied to the type current output. When the option [SV2] or [CR5] is applied, the option [W1X] cannot be applied together. Rating : 5A [Option W10], 10A [Option W11], 20A [Option W12] or 50A [Option W15] Setting range : In the case of 5A, 0.0 to 5.0A (off when set to 0.0) In the case of 10A, 0.0 to 10.
Operating Instructions Temperature Indicating Controller CF1M Phenomenon If it is impossible to set. If the value does not change by the , keys. If the setting indication does not change in the rated scale range even if keys the , are pressed, and setting is impossible. Phenomenon If process variable (temperature) does not rise. If the main output remains ON status. If the main output remains OFF status.