5.2 Main setting mode
Character Name, Function, Setting range Default value
SV1
Sets set value 1.
Setting range: SV low limit to SV high limit
0 °C
SV2
Sets set value 2.
Available only when the option [SV2] is applied.
Setting range: SV low limit to SV high limit
0 °C
5.3 Sub setting mode
Character Name, Function, Setting range Default value
AT setting/Auto-reset setting
Designates auto-tuning Performance or auto-reset Performance.
If the auto-tuning is cancelled during the process, P, I and D
values revert to the former value at which AT is performed.
When auto-tuning has not finished after 4 hours, it is cancelled
automatically.
Auto-reset is cancelled in approximately 4 minutes.
OUT1 proportional band setting
Sets the proportional band for OUT1.
OUT1 becomes ON/OFF action when set to 0 … 0.0
0 … 1000 °C (2000 °F), 0.0 … 999.9 °C (°F) or 0.0 … 100.0 %
10 °C
OUT2 proportional band setting
Sets the proportional band for OUT2.
OUT2 becomes ON/OFF action when OUT1 proportional band is
set to 0 or 0.0.
Not available if option [DT2] is not added or if OUT1 is ON/OFF
action.
0.0 … 10.0 times (multiplying factor to OUT1 proportional band)
1.0 times
Integral time setting
Sets integral time for OUT1.
Setting the value to 0 disables the function.
Not available when OUT1 is ON/OFF action.
Auto-reset can be performed when PD action (I=0).
Setting range: 0 … 1000 seconds
200 seconds
Derivative time setting
Sets derivative time for OUT1.
Setting the value to 0 disables the function.
Not available when OUT1 is ON/OFF action.
Setting range: 0 … 300 seconds
50 seconds
ARW setting
Sets ARW for OUT1.
Available only when PID is the control action.
Setting range: 0 … 100 %
50 %
OUT1 proportional cycle setting
Sets proportional cycle for OUT1.
Not available for control output analogue current signal or when
OUT1 is ON/OFF action.
Setting range: 1 … 120 seconds
30 seconds or
3 seconds