Instruction Manual

Operating Instructions Temperature Indicating Controller CS4S
V1.1
10/2006 - 28 -
9. Specifications
9.1 Standard specifications
Mounting method
: Flush
Setting method : Input system using membrane sheet key
Display PV display : Red LED 4 digits, character size 10.2 x 4.9 mm (H x W)
SV display : Green LED 4 digits, character size 8.8 x 4.9 mm (H x W)
Accuracy (Setting and Indication):
Thermocouple : Within ±0.2 % of each input span ±1digit, or within ±2 °C (4 °F),
whichever is greater
However R, S inputs 0 … 200 °C (400 °F): Within ±6 °C (12 °F)
B input, 0 … 300 °C (600 °F): Accuracy is not guaranteed
K, J, E, T, N inputs less than 0 °C (32 °F): Within ±0.4 % of input span±1digit
RTD : Within ±0.1 % of each input span ±1 digit, or
within ±1 °C (2 °F), whichever is greater
DC current : Within ±0.2 % of each input span ±1 digit
DC voltage : Within ±0.2 % of each input span ±1 digit
Input sampling period : 0.25 seconds
Input Thermocouple : K, J, R, S, B, E, T, N, PL- , C(W/Re5-26)
External resistance : 100
Ω or less
(However, B input: External resistance: 40
Ω or less)
RTD : Pt100, JPt100, 3-wire system
Allowable input lead wire resistance : 10
Ω or less per wire
DC current : 0 … 20mA DC, 4 … 20mA DC
Input impedance : External shunt resistor 50
Ω
Allowable input current : 50mA or less
DC voltage : 0 … 1V DC
Input impedance : 1 M
Ω or greater
Allowable input voltage : 5 V or less
Allowable signal source resistance : 2 k
Ω or less
: 0 … 5V DC, 1 … 5V DC, 0 … 10V DC
Input impedance : 100 k
Ω or greater
Allowable input voltage : 15 V or less
Allowable signal source resistance : 100
Ω or less
OUT1 output
Relay contact : 1a, Control capacity 3 A 250 V AC (resistive load)
1 A 250 V AC (inductive load cosø = 0.4)
Electrical life 100,000 times
Logic level DC 0/12 V (non contact voltage for SSR drive):
12
+ 2
- 0
V DC maximum 40 mA (short circuit protected)
analogue current signal:
4 … 20 mA DC, Load resistance maximum 550
Ω
A1 output
Action : ON/OFF action
Hysteresis : 0.1 … 100.0 °C (°F), or 1 … 1000
Output : Relay contact 1a
Control capacity 3 A 250 V AC (resistive load)
Electrical life 100,000 times