Instruction Manual

Operating Instructions Temperature Indicating Controller CS4S
V1.1
10/2006 - 8 -
3. Mounting to control panel
3.1 Site selection
This instrument is intended to be used under the following environmental conditions (IEC61010-1):
Overvoltage category
, Pollution degree 2
Mount the controller in a place with:
A minimum of dust, and an absence of corrosive gases
No flammable, explosive gasses
Few mechanical vibrations or shocks
No exposure to direct sunlight
An ambient temperature of 0 … 50 °C (32 … 122 °F), which does not change rapidly
An ambient non-condensing humidity of 35 … 85 %RH
No large capacity electromagnetic switches or cables through which large current is flowing
No water, oil or chemicals or where the vapors of these substances can come into direct contact with the
controller
3.2 External dimension
(Fig. 3.2-1)
3.3 Panel cutout
Lateral close mounting
n: Number of units mounted
Caution: If lateral close mounting is used for the
controller, IP66 specification will not be fulfilled.
(Fig. 3.3-1)
75
45
+0.5
0
45
+0.5
0
45
+0.5
0
n x 48-3
+0.5
0
48
11.5
95
44.5
59.7
Gasket
Screw type mounting bracket