4.3 Mounting steps
For mounting IPT-1* Vers. 2.0 a welded socket is necessary.
à Note the applicable welding standards (segment welding proce-
dure) when welding the socket.
Use the seal corresponding to the instrument:
l Process tting GD: Tesnit seal in front of the thread
- or -
Seal the thread with teon, hemp or a similar resistant seal material:
l Process tting ND
à Screw IPT-1* Vers. 2.0 into the welded socket. Tighten the
hexagon on the process tting with a suitable wrench. Wrench
size, see chapter "Dimensions".
Warning:
The housing must not be used to screw the instrument in! Applying
tightening force can damage internal parts of the housing.
Welding the socket
Sealing/Screwing in
12 Process pressure transmitter IPT-10 Vers. 2.0 - ceramic sensor Probus PA
4 Mounting