User guide
This function enables reading out parameter adjustment data as well
as writing parameter adjustment data into the sensor via the indicating
and adjustment module. A description of the function is available in the
operating instructions manual "Indicating and adjustment module".
The following data are read out or written with this function:
l Measured value presentation
l Adjustment
l Damping
l Linearisation curve
l Sensor-TAG
l Displayed value
l Scaling unit (Out-Scale unit)
l Positions after the decimal point (scaled)
l Scaling PA/Out-Scale 4 values
l Unit of measurement
l Language
The following safety-relevant data are not read out or written:
l Sensor address
l PIN
l Application
Copy sensor data
Copy sensor data?
Basic adjustment
If the "Reset" is carried out, the sensor resets the values of the
following menu items to the reset values (see chart):
8)
Menu section Function Reset value
Basic settings Unit of measurement bar
Temperature unit °C
Zero/Min. adjustment Measuring range begin
Span/Max. adjustment Measuring range end
Density 1 kg/l
Density unit kg/l
Damping 0 s
Linearisation linear
Sensor-TAG Sensor
Display Displayed value PA-Out
Service Additional PA value Secondary Value 1
Out-Scale-Unit Volume/l
Scaling 0.00 to 100.0
8)
Sensor-specific basic adjustment.
Copy sensor data
Reset
30 Process pressure transmitter IPT-10 Vers. 2.0 - ceramic sensor • Profibus PA
6 Set up with the indicating and adjustment module