Fig. 15: Sudden change of the process variable, dead time t
T
, rise time t
A
and step response time t
S
1 Process variable
2 Output signal
Dead time 150 ms
Rise time 100 ms (10 90 %)
Step response time 250 ms (ti: 0 s, 10 90 %)
Damping (63 % of the input variable) 0 999 s, adjustable
Additional output parameter - temperature
Processing is made via output signal HART multidrop, Probus PA and Foundation Fieldbus
Range -50 +150 °C (-58 +302 °F)
Resolution 1 °C (1.8 °F)
Accuracy
- in the range of 0 +100 °C
(+32 +212 °F)
±3 K
- in the range of -50 0 °C (-58 +32 °F)
and +100 +150 °C (+212 +302 °F)
typ. ±4 K
Input variable
Adjustment
Adjustment range of the min./max. adjustment relating to the nominal measuring range:
- percentage value -10 110 %
- pressure value -20 120 %
Process pressure transmitter IPT-10 Vers. 2.0 - ceramic sensor Probus PA 41