Indicating and adjustment module
Voltage supply and data transmission through the sensor
Indication LC display in dot matrix
Adjustment elements 4 keys
Protection
- unassembled IP 20
- mounted into the sensor without cover IP 40
Materials
- Housing ABS
- Inspection window Polyester foil
Power supply
Operating voltage
- Non-Ex instrument 9 32 V DC
- EEx-ia instrument 9 24 V DC
Operating voltage with lighted indicating and adjustment module
- Non-Ex instrument 12 36 V DC
- EEx-ia instrument 12 30 V DC
Power supply by DP/PA segment coupler
max. number of sensors 32 (10 with Ex)
Electrical protective measures
Protection
- Housing, standard IP 66/IP 67
15)
Overvoltage category III
Protection class II
Approvals
Depending on the version, instruments with approvals can have dierent technical data. For these
instruments, please note the corresponding approval documents. They are included in the scope
of delivery.
15)
Instruments with gauge pressure measuring ranges cannot detect the am-
bient pressure when submerged, e.g. in water. This can lead to falsication
of the measured value.
46 Process pressure transmitter IPT-10 Vers. 2.0 - ceramic sensor Probus PA
10 Supplement