Fig. 15: Sudden change of the process variable, dead time t
T
, rise time t
A
and step response time t
S
1 Process variable
2 Output signal
Dead time 150 ms
Rise time 100 ms (10 90 %)
Step response time 250 ms (ti: 0 s, 10 90 %)
Damping (63 % of the input variable) 0 999 s, adjustable
Input variable
Adjustment
Adjustment range of the min./max. adjustment relating to the nominal measuring range:
- Min. -5 +95 %
- Max. -5 +105 %
Adjustment range of the zero/span adjustment relating to the nominal measuring range:
- zero -5 +95 %
- Span -5 +105 %
Recommended max. turn down 10 : 1 (no limitation)
Nominal measuring ranges and overload resistance
Nominal range Overload, max. pressure Overload, min. pressure
Gauge pressure
0 0.4 bar/0 40 kPa 2 bar/200 kPa -1 bar/-100 kPa
0 1.6 bar/0 160 kPa 10 bar/1000 kP a -1 bar/-100 kPa
0 16 bar/0 1.6 MPa 80 bar/8 MPa -1 bar/-100 kPa
0 40 bar/0 4 MPa 80 bar/8 MPa -1 bar/-100 kPa
0 100 bar/0 10 MPa 200 bar/20 MPa -1 bar/-100 kPa
0 250 bar/0 25 MPa 500 bar/50 MPa -1 bar/-100 kPa
0 600 bar/0 60 MPa 1200 bar/120 MPa -1 bar/-100 kPa
Process pressure transmitter IPT-1* Vers. 3.0 - metalic sensor Probus PA 41