Instruction Manual

Nominal range Overload, max. pressure Overload, min. pressure
-1 3 bar/-100 300 kPa 17 bar/1700 kP a -1 bar/-100 kPa
-1 5 bar/-100 500 kPa 35 bar/3500 kP a -1 bar/-100 kPa
-1 15 bar/-100 1.5 MPa 80 bar/8 MPa -1 bar/-100 kPa
Absolute pressure
0 0.4 bar/0 40 kPa 2 bar/200 kPa
0 bar abs.
0 1.6 bar/0 160 kPa 10 bar/1000 kP a
0 bar abs.
0 6 bar/0 600 kPa 35 bar/3500 kP a
0 bar abs.
0 16 bar/0 1.6 MPa 80 bar/8 MPa
0 bar abs.
Reference conditions and actuating variables (similar to DIN EN 60770-1)
Reference conditions according to DIN EN 61298-1
- Temperature +18 +30 °C (+64 +86 °F)
- Relative humidity 45 75 %
- Air pressure 860 1060 mbar/86 106 kPa (12.5 15.4 psig)
Determination of characteristics Limit point adjustment according to IEC 61298-2
Characteristics linear
Reference installation position upright, diaphragm points downward
Inuence of the installation position depending on the isolating diaphragm version
Deviation determined according to the limit point method according to IEC 60770
14)
Applies to digital interfaces (HART, Probus PA, Foundation Fieldbus) as well as to analogue
current output 4 20 mA. Specications refer to the set span. Turn down (TD) is the relation
nominal measuring range/set span.
Deviation for measuring ranges 0.4 1000 bar
- Turn down 1 : 1 up to 5 : 1 < 0.1 %
- Turn down > 5 : 1 < 0.02 % x TD
Deviation for measuring ranges > 1000 bar
- Turn down 1 : 1 up to 2 : 1 < 0.6 %
Deviation with absolute pressure measuring range 0.1 bar
- Turn down 1 : 1 up to 5 : 1 < 0.25 %
- Turn down > 5 : 1 < 0.05 % x TD
Inuence of the product or ambient temperature
Applies to instruments with digital signal output (HART, Probus PA, Foundation Fieldbus) as well
as to instruments with analogue current output 4 20 mA. Specications refer to the set span.
Turn down (TD) = nominal measuring range/set span.
14)
Incl. non-linearity, hysteresis and non-repeatability.
42 Process pressure transmitter IPT-1* Vers. 3.0 - metalic sensor Probus PA
10 Supplement