4 Mounting
4.1 General instructions
Make sure that all parts of the instrument in contact with the measured
product, especially the sensor element, process seal and pr ocess
fitting, are suitable for the existing process conditions such as process
pressure, process temperature as well as the chemical properties of
the medium.
You can find the specifications in chapter "Technical data" in the or on
the type label.
Select an installation position you can easily reach for mounting and
connecting as well as later retrofitting of an indicating and adjustment
module. The housing can be rotated by 330° without the use of any
tools. You can also install the indicating and adjustment module in four
different positions (each displaced by 90°).
The ventilation of the measuring cell is realised by a filter element in
the socket of the electronics housing. The ventilation of the electronics
housing is realised via an additional filter element around the cable
glands.
1)
1
2
Fig. 2: Position of the filter elements
1 Filter element for ventilation of the measuring cell
2 Filter element for ventilation of the electronics housing
Information:
Make sure that the filter elements are always free of buildup during
operation. A pressure washer must not be used for cleaning.
Higher process temperatures mean often also higher ambient
temperatures.
1)
With previous instrument versions, ventilation and pressure compensation
were carried out together via a filter element.
Suitability for process
conditions
Mounting position
Ventilation and pressure
compensation
Temperature limits
10 Process pressure transmitter IPT-10 Vers. 2.0 - ceramic sensor • 4 … 20 mA/HART
4 Mounting