Manual
1
2
Fig. 3: Temperature ranges
1 Process temperature
2 Ambient temperature
Make sure that the upper temperature limits for the environment of
electronics housing and connection cable specified in chapter
"Technical data" are not exceeded.
4.2 Mounting instructions
IPT-10 functions in any installation position. It is mounted according to
the same directives as a manometer (DIN EN 839-2).
2)
Information:
We recommend using lock fittings, measuring instrument holders and
siphons from the line of WIKA accessories.
4.3 Mounting steps
For mounting IPT-10 a welded socket is necessary.
à Note the applicable welding standards (segment welding proce-
dure) when welding the socket.
Use the seal corresponding to the instrument:
l Process fitting GD: Tesnit seal in front of the thread
- or -
Seal the thread with teflon, hemp or a similar resistant seal material:
l Process fitting ND
2)
Probable position correction see chapter "Setup steps".
Mounting position
Welding the socket
Sealing/Screwing in
Process pressure transmitter IPT-10 Vers. 2.0 - ceramic sensor • 4 … 20 mA/HART 11