Manual
10 Supplement
10.1 Technical data
General data
Parameter, pressure Gauge pressure, absolute pressure, vacuum
Measuring principle Ceramic-capacitive, dry measuring cell
Service interface I²C bus
Materials and weights
316L corresponds to 1.4404 or 1 .4435
Materials, wetted parts
- Process fitting 316L, Hastelloy C276/C4, Titanium Grade 2, PVDF
- Diaphragm sapphire ceramic
®
(99.9 % oxide ceramic)
- Joining material diaphragm/Basic ele-
ment measuring cell
Glass solder
- Measuring cell seal FKM (A+P 70.16-06), FFKM (Kalrez 6375), EPDM
(A+P 75.5KW/75F), silicone, FFKM (Chemraz 535)
- Seal, process fitting Klingersil C-4400, Tesnit
Materials, non-wetted parts
- Electronics housing Plastic PBT (polyester), Alu die-casting powder-
coated, 316L
- Seal, housing cover Silicone
- Inspection window in housing cover for
indicating and adjustment module
Polycarbonate (UL-746-C listed)
- Ground terminal 316Ti/316L
Weight approx. 0.8 kg (1.764 lbs)
Output variable
Output signal 4 … 20 mA/HART
HART output values
- HART value (Primary Value) Process pressure
- HART value (Secondary Value) Temperature
Signal resolution 1.6 µA
Failure signal current output (adjustable) mA-value unchanged 20.5 mA, 22 mA, < 3.6 mA
Max. output current 22 mA
Load see load diagram under Power supply
Fulfilled NAMUR recommendations NE 43
Process pressure transmitter IPT-10 Vers. 2.0 - ceramic sensor • 4 … 20 mA/HART 43
10 Supplement