User guide

The adjustment unit is hence switched over from bar to m.
Proceed as follows to select the temperature unit:
6)
à Activate the selection with [OK] and select "Temperature unit
with [->].
à Activate the selection with [OK] and select the requested unit with
[->] (e.g. °F).
à Conrm with [OK].
The temperature unit is hence switched over from °C to °F.
Proceed as follows:
1 Activate in the menu item "Position correction" the selection with
[OK].
Position correction
Oset
=
+0000 mbar
53 mbar
2 Select with [->], e.g. to accept actual measured value.
Position correction
Accept current measured
value?
Accept
Edit
3 Conrm with [OK] and move to min.(zero) adjustment with [->].
Proceed as follows:
1 Edit the % value in the menu item "Min. adjustment" with [OK].
Min. adjustment
+000.0 %
=
+0000.0 mbar
0000.0 mbar
2 Set the requested percentage value with [+] and [->].
3 Edit the requested mbar value with [OK].
4 Set the requested mbar value with [+] and [->].
5 Conrm with [+] and move to max. adjustment with [->].
The min. adjustment is nished.
Information:
For an adjustment with lling, you simply enter the displayed actual
measured value. If the adjustment ranges are exceeded, the message
"Outside parameter limits" appears. The editing procedure can be
6)
Selection options: °C, °F.
Carry out position cor-
rection
Carrying out min. ad-
justment
Process pressure transmitter IPT-1* Vers. 3.0 - metalic sensor Foundation Fieldbus 25
6 Set up with the indicating a nd adjustment module