In Ex applications, the regulations for the wiring of intrinsically safe
circuits must be observed.
? E013
l no measured value available
11)
à Exchange instrument or return instrument for repair
? E017
l Adjustment span too small
à repeat with modied values
? E036
l no operable sensor software
à Carry out a software update or send the instrument for repair
? E041
l Hardware error, electronics defective
à Exchange instrument or return instrument for repair
? E113
l Communication conict
à Exchange instrument or return instrument for repair
Depending on the failure reason and measures taken, the steps
described in chapter "Set up" must be carried out again, if necessary.
8.3 Instrument repair
You can download a return form (24 KB) in the Internet from our
homepage www.wika.com under the item "Service".
If a repair is necessary, please proceed as follows:
l Print and ll out one form per instrument
l If necessary, state a contamination
l Clean the instrument and pack it damage-proof
l Attach the completed form and probably a safety data sheet to the
instrument
l Please contact the agency serving you for the address of the
return shipment
By doing this you help us carry out the repair quickly and without
having to call back for needed information.
11)
Fault message can also appear if the pressure is higher than the nominal
range.
Fault messages via the
indicating/adjustment
module
Reaction after fault rec-
tication
Process pressure transmitter IPT-1* Vers. 3.0 - metalic sensor Foundation Fieldbus 37
8 Maintenance and fault rectication