User guide
Product temperature standard, depending on the seal
17)
- FKM (VP2/A) -20 … +105 °C (-4 … +221 °F)
- EPDM (A+P 75.5/KW75F) -40 … +105 °C (-40 … +221 °F)
- NBR (COG) -20 … +105 °C (-4 … +221 °F)
Product temperature front-flush threaded fitting G1 A according to EHEDG, threaded fitting
M44 x 1 .25 as well as hygienic fittings, depending on seal
18) 19)
- FKM (VP2/A) -20 … +150 °C (-4 … +302 °F)
- EPDM (A+P 75.5/KW75F) -30 … +150 °C (-22 … +302 °F)
- NBR (COG) -20 … +150 °C (-4 … +302 °F)
Vibration resistance mechanical vibrations with 4 g and 5 … 100 Hz
20)
Shock resistance Acceleration 100 g/6 ms
21)
Electromechanical data - version IP 66/IP 67
Cable entry/plug
22)
- Single chamber housing l 1 x cable gland M20 x 1.5 (cable: ø 5 … 9 mm),
1 x blind stopper M20 x 1.5
or:
l 1 x closing cap ½ NPT, 1 x blind plug ½ NPT
or:
l 1 x plug (depending on the version), 1 x blind
stopper M20 x 1.5
- Double chamber housing l 1 x cable entry M20 x 1.5 (cable: ø 5 … 9 mm),
1 x blind stopper M20 x 1.5; plug M12 x 1 for
the external indicating and adjustment module
(optional)
or:
l 1 x closing cap ½ NPT, 1 x blind stopper
½ NPT, plug M12 x 1 for the external indicating
and adjustment module (optional)
or:
l 1 x plug (depending on the version), 1 x blind
stopper M20 x 1.5; plug M12 x 1 for the
external indicating and adjustment module
(optional)
Spring-loaded terminals for wire cross-sec-
tion up to
2.5 mm² (AWG 14)
17)
Version for oxygen applications up to 60 °C (140 °F).
18)
Not with hygienic fitting with compression nut F40 PN40/316L
19)
Version for oxygen applications up to 60 °C (140 °F).
20)
Tested according to the regulations of G erman Lloyd, GL directive 2.
21)
Tested according to EN 60068-2-27.
22)
Depending on the version M12 x 1, according to DIN 43650, Harting, 7/
8" FF.
Process pressure transmitter IPT-1* Vers. 3.0 - metalic sensor • Foundation Fieldbus 43
10 Supplement
31545-EN-081211










