User guide
Secondary_value_2
scale_in_0 scale_in_100 Sensor_value
0 %
100 %
bar
0,500-0,500
0
%
100
%
scale_in_100scale_in_0
Fig. 17: Adjustment IPT-1* Vers. 3.0
Parameter list
The following list contains the most important parameters and their meaning:
l primary_value
- Process Value after min/max-adjustment and linearization. Selected as input to AIFB by setting
'Channel' = 1. Unit derives from 'Primary_value_unit'
l primary_value_unit
- Unit code of 'Primary_value'
- %
l secondary_value_1
- Process pressure. Selected as input to AIFB by setting 'Channel' = 2. Unit derives from
'Secondary_value_1_unit'
l secondary_value_1_unit
- Unit code of 'Secondary_value_1'
- bar, PSI, …, m, ft, …; in case of length type engineering unit and access to parameters the
corresponding values will be converted by density factor
l secondary_value_2
- Value after min/max-adjustment. Selected as input to AIFB by setting 'Channel' = 3. Unit derives
from 'Secondary_value_2_unit'
l secondary_value_2_unit
- Selected unit code for "secondary_value_2"
l sensor_value
- Raw sensor value, i.e. the uncalibrated measurement value from the sensor. Unit derives from
'Sensor_range.unit'
46 Process pressure transmitter IPT-1* Vers. 3.0 - metalic sensor • Foundation Fieldbus
10 Supplement