Instructions / Assembly
Installing Your Furnace 
16 
Attaching Your Furnace (continued)
After furnace is in position, install rear outlet register as shown in 
Figure 12. Have damper in open position when inserting the 
assembly. Secure the rear outlet register to speed nuts with the 
machine screws furnished.
Gas Supply and Piping 
GAS PIPING 
The gas supply line must be of adequate size to handle the Btu/hr. 
requirements and length of the run for the unit being installed. 
Determine the minimum pipe size from Figure 17, basing the 
length of the run from the gas meter or source to the unit.  
All piping must comply with local codes and ordinances or with the 
National Fuel Gas Code (ANSI Z223.1 NFPA No. 54), whichever 
applies. (In Canada: CAN/C.G.A B149). Refer to Figure 18 for 
the general layout of the unit. It shows the basic fittings needed. 
The following rules apply: 
1.  Use new, properly reamed pipe free from chips such as 
steel or black iron pipe and fittings or other approved by 
local codes. 
2.  Do not thread pipe too far. Valve distortion or malfunction 
may result from excess pipe within the control. Apply a 
moderate amount of good quality dope to pipe only. Leave 
the two end threads bare. If L.P. gas installation, use 
compound resistant to action of liquefied petroleum gases. 
3.  Use ground joint unions. 
4.  Install a drip leg (sediment trap) to trap dirt and moisture 
before it can enter the gas valve. The nipple must be a 
minimum of 3-inches long.  
5.  Install a manual shut-off valve. 
6.  Provide a 1/8 NPT test gauge connection immediately 
before the gas supply connection to the furnace. 
2509622A Nat. 25,000 18,935 #43 0.089 1
2509621A L.P. 25,000 19,759 .057" 1
3509622A Nat. 35,000 24,496 #36 0.106 1
3509621A L.P. 35,000 25,588 .069" 1
5009622A Nat. 50,000 38,490 .091" 2
5009621A L.P. 50,000 39,827 .058" 2
Furnace Technical Information
Main Burner Orifice
Drill
Decimal
Quantity
Heating 
Capacity 
Rating 
Btu/hr.
Input    
Rating    
Btu/hr.
Gas 
Type
Model   
Number
Gas Supply and Piping (continued)
FIGURE 12 – Mounting Rear Outlet Register 
The gas control valve, in the furnace, is shipped with a seal over 
the  gas  inlet  tapping.   Do  not  remove the  seal  until  ready  to 
connect the piping. 
GAS SUPPLY 
For L.P.  gas,  the minimum inlet  gas supply pressure  for the 
purpose  of  input  adjustment  is  11-inches  water  column.  The 
maximum inlet gas supply pressure is 13-inches water column. 
For  natural  gas,  the  minimum  inlet  gas  supply  pressure  for  the 
purpose  of  input  adjustment  is  5-inches  water  column.  The 
maximum inlet gas supply pressure is 7-inches water column. 
Gas pressure and input to the burners must not exceed the rated 
input  and  pressure  shown  on  the  nameplate.    The  natural  gas 
manifold  pressure  should  be  4-inches  water  column.    The 
manifold pressure should be 10-inches water column for L.P. gas. 
For operation  in elevations  above 2,000 feet,  a  burner  orifice 
change  may  be  required  to  suit  the  gas  supplied.    Check  with 
your local gas supplier. 
ORIFICE SIZES  
The  efficiency  rating  of  this  appliance  is  a  product  thermal 
efficiency  rating  determined  under  continuous  operating 
conditions and  was  determined  independently  of  any installed 
system.  For elevations above 2,000 feet, reduce ratings 4% for 
each 1,000 feet above sea level.  
WARNING:  Danger  of  property  damage,  bodily  injury or 
death.    Make  sure  the  furnace  is  equipped  to  operate  on 
the type of gas available.  Models designed as natural gas 
are to be used with natural gas only.  Models designed for 
use  with  liquefied  petroleum  (L.P)  gas  have  orifices  sized 
for commercially pure propane gas.  They cannot be used 
with butane or a mixture of butane and propane. 
Gas Conversion Kits 
Natural Gas to L.P. Gas 
Model 
Description 
8913 
25096A Series with Williams Brand Gas Valve 
8914 
35096A Series with Williams Brand Gas Valve 
8909 
50098 Series with Williams Brand Gas Valve 
Gas Conversion kits 
L.P. Gas to Natural Gas 
Model 
Description 
8915 
25096A Series with Williams Brand Gas Valve 
8916 
35096A Series with Williams Brand Gas Valve 
8912 
50098 Series with Williams Brand Gas Valve 
Furnace Technical Information 










