Operating instructions
11
Part Number 550-142-784/0812
GWA
Series 2 Gas-Fired Water Boilers – Boiler Manual
Near-boiler piping continued
Figure 7 Piping refrigeration systems
Water piping — refrigeration systems
Prevent chilled water from entering boiler
Installboilersothatchilledmediumispipedinparallelwiththe
heatingboiler.Useappropriatevalvestopreventchilledmedium
from entering boiler. See Figure 7 for typical installation of
balancingvalveandcheckvalve.
Ifsystemincludesradiantheatingcircuits,provide
piping and controls to regulate the temperature
supplying the radiant circuits. Failure to comply could
result in substantial property damage.
UseFigure 5 or Figure 6onlyforsystemsdesigned
forreturn wateratleast 130°F.Forsystems with
low return water temperature possible, such as
converted gravity systems and radiant heating
systems, install bypass piping (see page 12) to
protect boiler against condensation. Failure to
prevent low return water temperature to the boiler
could cause corrosion of the boiler sections or
burners, resulting in severe personal injury, death
or substantial property damage.
Install boiler so that chilled medium is piped
in parallel with heating boiler (Figure 7). Use
appropriatevalvestopreventchilledmediumfrom
enteringboiler.ConsultAHRIInstallationandPiping
Guides.
If boiler is connected to heating coils located in
air handling units where theycan be exposed to
refrigerated air, use owcontrol valves or other
automatic means to prevent gravity circulation
during cooling cycle. Circulation of cold water
through the boiler could result in damage to the heat
exchanger,causingpossibleseverepersonalinjury,
death or substantial property damage.
Figure 5 Diaphragm- or bladder-type expansion tank:
Piping to single-zone system using
diaphragm-type or bladder-type expansion
tank. See Table 4 for piping sizes.
3 Install water piping continued
Figure 6 Closed-type expansion tank: Piping to single-
zone system using closed-type expansion
tank. See Table 4 for piping sizes.