Operating instructions
15
Part Number 550-142-784/0812
GWA
Series 2 Gas-Fired Water Boilers – Boiler Manual
Fill the system with water
1. Closemanualandautomaticairventsandboilerdraincock.
2. Fill to correct system pressure. Correct pressure will vary
with each application.Typical cold water ll pressure for a
residential system is 12 psi.
3. Purgeairfromsystem:
a. Connectahosetopurgevalveorvalves,ifinstalled.Route
hose to an area where water can drain and be seen.
b. Close the boiler or system isolation valve between the
purge valve and fill connection to the system.
c. Closezoneisolationvalves.
d. Openquick-llvalveoncoldwatermakeupline.
e. Open purge valve.
f. One zone at a time, open the isolation valves. Allow
water to run through the zone, pushing out the air. Run
until no noticeableair ow is present. Close the zone
isolationvalvesandproceedwiththenextzone.Follow
this procedure until all zones are purged.
g. Closethequick-llwatervalveandpurgevalveandremove
the hose. Open all isolation valves. Watch that system
pressure rises to correct cold-fill pressure.
h. After the system has operated for a while, eliminate
any residual air by using the manual air vents located
throughout the system.
i. Ifpurgevalvesarenotinstalledinsystem,openmanualair
vents in system one at a time, beginning with lowest floor.
Closeventwhenwatersquirtsout.Repeatwithremaining
vents.
4. Open automatic air vent (diaphragm-type or bladder-type
expansiontanksystemsonly)oneturn.
5. Open other vents:
a. Starting on the lowest floor, open air vents one at a time
until water squirts out.
b. Repeat with remaining vents.
6. Refill to correct pressure.
Inspect system water piping
Afterllingtheboilerandsystemwith water,inspectallpiping
throughout the system for leaks. If found, repair immediately.
Repeatthisinspectionaftertheboilerhasbeenstartedandthe
system has heated up.
Leaksmustberepairedatonce.Failuretodosocan
damage the boiler, resulting in substantial property
damage.
Do not use petroleum-based cleaning or sealing
compounds in boiler system. Severe damage to boiler
will occur, resulting in substantial property damage.
Determine if water treatment is needed
Do not use petroleum-based cleaning or sealing
compounds in boiler system. Severe damage to
boiler will occur, resulting in substantial property
damage.
Eliminateallsystemleaks.Continualfreshmakeup
waterwillreduceboilerlife.Mineralscanbuildup
insections,reducingheattransfer,overheatingcast
iron,andcausingsectionfailure.
Verify water chemistry
Consultlocalwatertreatmentcompaniesforunusuallyhardwater
areas (above 7 grains hardness) or low pH water conditions (below
7.0).BoilerwaterpHof7.0to8.5isrecommended.
Freeze protection (when used)
Useantifreezemadeespeciallyforhydronicsystems. Inhibited
propylene glycol is recommended.
Do not use ethylene glycol, automotive or undiluted
antifreeze.Severepersonalinjuryordeathcanresult.
1. Determine antifreeze quantity according to system water
content. Boiler water content is listed on Page 46. Remember
toincludeexpansiontankwatercontent.
2. Followantifreezemanufacturer’sinstructions.
3. A50%solutionofpropyleneglycol/waterprovidesmaximum
protection to about -30 °F.
4. Local codes may require back flow preventer or actual
disconnectfromcitywatersupply.
5. Whenusingantifreezeinasystemwithautomaticll,installa
watermetertomonitorwatermakeup.Glycolwillleakbefore
thewaterbeginstoleak,causingglycolleveltodrop.Added
waterwilldilutetheantifreeze,reducingthefreezeprotection
level.
Check for gas leaks
Beforestartingtheboiler,andduringinitialoperation,
smellneartheoorandaroundtheboilerforgas
odorant or any unusual odor. Do not proceed with
start-upifthereisanyindicationofagasleak.Repair
anyleakatonce.
Propaneboilersonly—Yourpropanesuppliermixes
anodorantwiththepropanetomakeitspresence
detectable.Insomeinstances,theodorantcanfade
and the gas may no longer have an odor.
• Propanegascanaccumulateatoorlevel.Smell
neartheoorforthegasodorantoranyunusualodor.
Ifyoususpectaleak,donotattempttolightthepilot.
• Usecautionwhenattemptingtolightthepropane
pilot. This should be done by a qualified service
technician,particularlyifpilotoutagesarecommon.
• Periodicallychecktheodorantlevelofyourgas.
• Inspectboilerandsystematleastyearlytomake
sureallgaspipingisleak-tight.
• Consultyourpropanesupplierregardinginstallation
ofagasleakdetector.Therearesomeproductson
themarketintendedforthispurpose.Yoursupplier
may be able to suggest an appropriate device.
6 Start-up
Preparation
Inspect base insulation
Checktomakesureinsulationissecureagainstallfoursidesof
thebase.Ifinsulationisdamagedordisplaced,donotoperate
boiler. Replace or reposition insulation.
Failure to replace damaged insulation or reposition
insulation can result in a fire hazard, causing
severe personal injury, death or substantial property
damage.
The boiler contains ceramic fiber and fiberglass
materials.Usecarewhenhandlingthesematerials
per instructions on page 39ofthismanual.Failure
to comply could result in severe personal injury.