GWC gas-fired water boilerBoiler Manual
Troubleshooting (continued)
CHART 7
LIMIT light flashing and POWER light on steady
Electrical shock hazard — Wherever you see TURN OFF POWER, follow the instructions. Failure to follow
instructions could result in severe personal injury, death or substantial property damage.
Remove SENSOR plug from receptacle on IBC (Figure 89, page 76, Item 6).
Then re-insert.
Does LIMIT light still flash?
No Yes
Replace sensor and harness.
Does LIMIT light still flash?
No Yes
Boiler may now be operating correctly. Verify per normal
sequence of operation (Figure 71, page 63).
Replace IBC.
Retest.
This is NOT a lockout mode. The IBC should only be signal-
ing that the water temperature sensor is either shorted or
there is an open circuit across the sensor terminals.
This situation is usually corrected by replacing the sensor,
as described below.