Specification

5146694-BTG-C-0616
Johnson Controls Unitary Products 61
PERFORMANCE DATA - 4 TON
Multipliers for determining the performance with other indoor sections.
NOTE: For dry bulb temperatures different than those listed (between 73-87 °F), sensible capacity increases by 1060 BTUH per 1000 CFM per degree above the listed
temperature and decreases by 1060 BTUH per 1000 CFM per degree below the listed temperature.
CONDENSER-ONLY DATA (OUTDOOR UNIT)
MODEL
SATURATED SUCTION
@ COMPRESSOR
Outdoor Ambient Temperature
55 °F 65 °F 75 °F 85 °F 95 °F 105 °F 115 °F
T (°F) P (PSIG) MBH KW MBH KW MBH KW MBH KW MBH KW MBH KW MBH KW
TC3B4821S
35 107 46.2 2.20 44.0 2.49 41.7 2.79 39.4 3.13 36.9 3.51 34.3 3.98 31.5 4.51
40 119 50.8 2.19 48.4 2.49 45.9 2.80 43.3 3.14 40.7 3.51 37.9 3.97 34.9 4.50
45 130 55.8 2.19 53.0 2.50 50.3 2.81 47.6 3.15 44.6 3.53 41.8 3.97 38.6 4.50
50 143 61.1 2.19 58.1 2.51 55.0 2.83 52.0 3.17 48.9 3.56 45.8 4.00 42.5 4.50
55 156 66.7 2.20 63.4 2.52 60.0 2.85 56.6 3.21 53.4 3.58 49.9 4.04 46.6 4.52
Notes:
1. For Outdoor Unit (Condenser) performance only. Data does not include the effects of air handler power or heat.
2. Performance based on 15°F subcooling and 15°F superheat at the Outdoor Unit base valves.
a. Increase capacity by 1% for each 2°F increase in subcooling.
b. Decrease capacity by 1% for each 2°F decrease in subcooling.
3. Maximum recommended condensing temperature is 140°F.
COOLING PERFORMANCE DATA
OUTDOOR UNIT MODEL NO. TC3B4821S
INDOOR COIL MODEL NO. CF48CXA1
AIR TEMP.
ENTERING
OUTDOOR UNIT (°F)
ID CFM 1400 1600 1800
ID DB (°F) 80 80 75 80 80 80 80 75 80 80 80 80 75 80 80
ID WB (°F) 57 62 62 67 72 57 62 62 67 72 57 62 62 67 72
55
T.C. 43.3 46.5 46.4 49.1 51.0 44.0 46.8 46.8 49.5 51.0 44.6 47.0 47.1 49.8 50.9
S.C. 42.7 36.7 32.2 30.5 23.8 43.4 38.0 33.1 31.3 24.2 44.0 39.4 34.0 32.2 24.6
KW 2.70 2.69 2.73 2.77 2.81 2.76 2.80 2.82 2.85 2.89 2.82 2.91 2.90 2.94 2.98
65
T.C. 43.2 46.0 45.9 48.8 51.5 44.1 46.4 46.4 49.2 51.5 45.0 46.8 47.0 49.7 51.6
S.C. 42.6 37.5 32.6 31.1 24.2 43.5 39.1 34.0 32.1 24.7 44.4 40.7 35.4 33.2 25.2
KW 2.99 2.96 3.02 3.06 3.10 3.04 3.05 3.10 3.14 3.18 3.09 3.15 3.18 3.22 3.27
75
T.C. 43.1 45.5 45.4 48.4 51.9 44.3 46.1 46.1 49.0 52.1 45.4 46.6 46.8 49.6 52.2
S.C. 42.5 38.4 33.1 31.7 24.6 43.7 40.2 34.9 32.9 25.2 44.8 41.9 36.8 34.1 25.9
KW 3.27 3.23 3.30 3.34 3.39 3.32 3.31 3.38 3.43 3.47 3.36 3.39 3.46 3.51 3.56
85
T.C. 41.5 43.5 43.1 47.2 50.8 43.1 44.0 43.8 47.5 50.6 44.7 44.5 44.6 47.9 50.5
S.C. 40.9 38.1 32.2 31.6 24.2 42.5 40.0 34.2 33.2 25.0 44.0 41.8 36.3 34.8 25.8
KW 3.58 3.63 3.65 3.72 3.78 3.65 3.69 3.74 3.80 3.87 3.72 3.75 3.82 3.89 3.95
95
T.C. 39.9 41.4 40.7 45.9 49.7 41.9 41.9
41.5 46.0 49.2 43.9 42.3 42.3 46.1 48.7
S.C. 39.4 37.9 31.3 31.5 23.9 41.3 39.8
33.5 33.5 24.8 43.2 41.7 35.7 35.5 25.7
KW 3.89 4.02 4.01 4.10 4.17 3.99 4.06
4.10 4.18 4.26 4.09 4.11 4.19 4.27 4.35
105
T.C. 37.6 38.3 37.4 42.3 46.8 39.3 39.3 38.0 42.7 46.4 41.0 40.4 38.7 43.1 46.1
S.C. 37.1 36.3 29.8 30.3 22.9 38.7 38.1 32.0 32.4 24.0 40.4 39.8 34.2 34.4 25.2
KW 4.33 4.39 4.45 4.56 4.66 4.44 4.47 4.54 4.65 4.75 4.54 4.55 4.63 4.74 4.85
115
T.C. 35.2 35.2 34.1 38.6 43.8 36.7 36.8 34.6 39.4 43.7 38.1 38.4 35.0 40.1 43.5
S.C. 34.7 34.7 28.4 29.1 21.9 36.2 36.3 30.5 31.2 23.3 37.6 37.9 32.7 33.4 24.7
KW 4.77 4.77 4.88 5.03 5.14 4.89 4.88 4.98 5.12 5.24 5.00 4.98 5.07 5.21 5.34
NOTE: ALL CAPACITIES INCLUDE INDOOR FAN HEAT. KW VALUES ARE FOR THE SYSTEM (OUTDOOR + INDOOR).
Green shaded cells are ACCA (TVA) conditions.
Blue shaded cells are AHRI conditions.