W10PTOS/A W15PTOS/F GENERATORS INSTALLATION AND OPERATORS MANUAL WINCO INC. 225 S. CORDOVA AVE. LE CENTER, MN 56057 507-357-6821 SERVICE DEPT. 507-357-6831 www.wincogen.
TABLE OF CONTENTS COPY YOUR MODEL AND SERIAL NUMBER HERE No other WINCO generator has the same serial number as yours. If you should ever need to contact us on this unit, it will help us to respond to your needs faster.
INTRODUCTION SPECIFICATIONS W10PTOS The WINCO rotating field power take-off generators are designed primarily for hobby/small farm use as a standby electrical power supply, utilizing the power take-off of a tractor or truck as the prime mover. This PTO drive generator will provide 120/240V single phase, 60Hz electrical service when properly driven. Watts 10,000 Amps 41.
SAFETY B. Keep your neighbors in mind when permanently installing this equipment. IMPORTANT SAFETY INSTRUCTIONS 4. CLEANLINESS - SAVE THESE INSTRUCTIONS Keep the generator and surrounding area clean. This manual contains important information that should be understood and followed before the installation, operation and maintenance of the generator. Failure to follow the safety instructions in this manual could result in serious injury or death. Keep this manual available for future reference. A.
TESTING POLICY E. For dimensions needed for install for your specific generator, please refer to it’s outline drawing. The hardware needed is dependent on your distinct application. Before any generator is shipped from the factory, it is fully checked for performance. The generator is loaded to its full capacity, and the voltage, current, and frequency are carefully checked. F. The generator mounting bracket must rest evenly and firmly on the foundation.
and generator input shafts. Misalignment must be less than 10 degrees during generator operation, even though the mechanical design of the tumbling bar would allow greater misalignment. A. The three point hitch must be attached to the tractor at all times The generator mounting area of the trailer bed should be duringD.operation. switch must in all cases be equal to or greater than the rating of the entrance rated breaker. B.
ELECTRICAL 7. Assemble cable clampCONNECTIONS over the outer jacket of the wire and WARNING: PERSONAL INJURY: tighten the two clamp screws. Special Note: For small size round Failure to wire as instructed may cause personal injury or damage to DANGER: PERSONAL INJURY (less than 3/4”) and flat cables, the wire clamp may be inverted. device or equipment. To be installed or checked an electrician or CAUTION: IF THE GENERATOR IS TO BE USEDbyAS A STANDBY qualified person only.
age of eding PRE-START CHECKS hich cost of a WARNING: PERSONAL INJURY: Make sure that all tumbling bar lock pins are engaged and that all safety shields are in place before operating the PTO generator. PRE-START WARNING: PERSONALCHECKS INJURY: When working on or around these generators, do NOT wear loose fitting clothing or Personal any articlesInjury that may get caught in moving parts. WARNING: e is plug f you ditional 7”. x.
NOTE: EQUIPMENT DAMAGE: If the load includes motors turn them on one at a time, highest starting current motor first, next highest second, etc CAUTION: EQUIPMENT DAMAGE Do not overfill generator gear case. Overfilling causes overheating and oil seal failure. 8. The return of normal power will be indicated by the lamp on the front of transfer switch; (applicable only when the transfer switch is equipped with indicating lamps or your electrician has installed them).
TROUBLE SHOOTING TABLE SYMPTOM POSSIBLE CAUSE CORRECTIVE ACTION Low Output Voltage 1. Undersized/overloaded. 2. Defective governor. 3. Low power - worn engine. 4. High line loss. Indicated by lower voltage at load than at generator terminals. 1.Check for overload on the tractor or undersized. 2. Check tractor governor. Tight or defective throttle levers and joints. 3. Worn or defective tractor engine. 4. Increase size of line wiring.
WIRING DIAGRAMS W10PTOS-3/A W10PTO WIRING DIAGRAM VOLTMETER GENERATOR 1 4 2 3 20A BREAKER 45A 240V BREAKER G3 ON N - G BOND N H G3 G3 OFF G1 20 AMP RCPT N H G H GND G1 G1 60 AMP RCPT GROUND LUG W15PTOS-3/E VOLTMETER W15PTO WIRING DIAGRAM GENERATOR 20A BREAKER V2 W1 U2 V1 W2 U1 60A 240V BREAKER G3 G1 N H G3 ON 20 AMP RCPT G3 OFF G1 G1 N G H 60 AMP RCPT H GND N - G BOND GROUND LUG REV C 11 60706-241
MONTH LIMITED WARRANTY WINCO, Incorporated warrants to the original purchaser for 12 months or 1000 hours which ever occurs first, that goods manufactured or supplied by it will be free from defects in workmanship and material, provided such goods are installed, operated and maintained in accordance with WINCO written instructions. WINCO’s sole liability, and Purchaser’s sole remedy for a failure under this warranty, shall be limited to the repair of the product.