COMPACT PTO GENERATORS OPERATOR INSTRUCTION MANUAL COMPACT SERIES TRACTOR DRIVE GENERATOR W15PTOS/E
TABLE OF CONTENTS SAFETY INFORMATION ......................................................................................................................................... SPECIFICATIONS ................................................................................................................................................... UNPACKING ............................................................................................................................................................
. SAFETY INFORMATION This generator set has been designed and manufactured to allow safe, reliable performance. Poor maintenance, improper or careless use can result in potential deadly hazards; from electrical shock, exhaust gas asphyxiation, or fire. Please read all safety instructions carefully before installation or use. Keep these instructions handy for future reference. Take special note and follow all warnings on the unit labels and in the manuals. a. b. 4. b.
DESCRIPTION UNPACKING The WINCO rotating field power take-off generators are designed primarily for hobby/small farm use as a standby electrical power supply, utilizing the power take-off of a tractor or truck as the prime mover. This PTO drive generator will provide 120/240V single phase, 60Hz electrical service when properly driven. CAUTION: Equipment Damage DO NOT invert generator during unpacking. The Gearcase contains oil which will leak out if inverted during unpacking.
the trailer should enable aligning the drive shaft (tumbling bar) in a straight or nearly straight line between the power take-off and generator input shafts. Misalignment must be less than 10 degrees during generator operation, even though the mechanical design of the tumbling bar would allow greater misalignment. D. The generator mounting area of the trailer bed should be flat. B. The foundation must be solid enough to absorb generator starting and reflected load torque during operation.
ELECTRICAL CONNECTIONS CAUTION: Only qualified electricians should install electrical wiring. Wiring must conform to all applicable national, state, and local codes. (Reference: National Fire Protection Association Manual No. 70, National Electrical Code.) DANGER: PERSONAL INJURY IF THE GENERATOR IS TO BE USED AS A STANDBY POWER SOURCE, A MANUAL TRANSFER SWITCH MUST BE INSTALLED TO SEPARATE THE GENERATOR AND THE COMMERCIAL POWER LINES.
A properly rated and installed double throw manual power isolation transfer switch must be used with a standby generator. The transfer switch isolates the load from the power line and allows you to safely operate your loads without endangering the power line repair crew. See page 4. The load, connected to the normal terminals of the transfer switch, is energized by the normal power line when the switch is in the normal position.
3. Make sure the drive shaft (tumbling bar) is assembled with its universal joint knuckles “synchronized,” as illustrated in Figure 7. If knuckles are not synchronized, the bar will chatter when rotating, which will cause the generator output voltage to flicker. Drive shafts shipped new from Winco are always synchronized and tethered so they can not be taken apart. to warm it up before proceeding, so that it will run smoothly and achieve full power under generator load. 3.
CLEANING STORAGE & MAINTENANCE If the generator is mounted on an off-highway trailer, such as the Winco trailer, it should be stored in a garage, barn or machine shed in a dry and clean location. The generator should be covered with a tarpaulin to prevent the entrance of dust, chaff, and/or moisture. The generator may be stored on end, provided the generator is on a clean, dry elevated surface such as a board. Do not have it resting on a dirt surface. (Figure 3) 1.
SERVICE DIAGNOSIS REMEDY POSSIBLE CAUSE LOW OUTPUT VOLTAGE Low Speed 1. 2. Undersized/overloaded. Defective governor. 3. Low power - worn engine. Check for overload on the tractor or undersized. Check tractor governor. Tight or defective throttle levers and joints. Worn or defective tractor engine (see engine manufacturers check list.) High line loss. Indicated by lower voltage at load than at generator terminals. Increase size of line wiring.
RECEPTACLE PANEL REF 1 2 3 4 5 6 7 NI PART # 300079-4 91370-000 300136 50766-000 91286-001 63708-000 57030-005 300137 QTY 1 1 1 1 1 1 1 1 DESCRIPTION Control Box Sheet Metal Voltmeter 0 - 300 VAC Receptacle, NEMA 14-60R Receptacle, NEMA 5-20R Circuit Breaker 20 AMP - 120 VAC Ground Lug Circuit Breaker 60 AMP - 240 VAC Plug.
COMPLETE UNIT ASSEMBLY REF PART # 1 99839-001 1 2 3 4 300077-6 99841-002 300160-6 1 1 1 5 300080-2 1 6 7 8 9 300086-1 15209-000 Z-2516 Z2553 1 1 1 1 60706-180 REF PART # Generator & Gear Case Assy S20F-230/A M5 Base Assembly Gear Case Support Receptacle Box Assembly 10 11 12 13 14 Z9941 Z2568 91369-003 53113-001 62487-003 NI 300323-112 1 Receptacle Box Cover Safety Shield Safety Decal Warning Decal Operating Instructions Decal NI 300323-212 2 NI 1 QTY DESCRIPTION NI Page 10 QT
TWO WHEEL TRANSPORT 1 2 3 4 5 6 7 8 0310-00 DESCRIPTION PART NO. SUPPORT, TONGUE (QTY. 2) HITCH, TONGUE (QTY. 2) TONGUE AXLE (QTY. 2) SUPPORT, AXLE SUPPORT, PTO SHAFT SUPPORT, PTO SHAFT TIRE/RIM, PNEUMATIC (QTY.
PTO GENERATOR 12 MONTH LIMITED WARRANTY WINCO, Inc., warrants for twelve months from date of shipment, that it will repair or replace at its option, for the original user, the whole or any part of the product found upon examination, by WINCO at its factory at 225 South Cordova Avenue, Le Center, Minnesota, or by any factoryauthorized service station, to be defective in material or workmanship under normal standby use.
0310-00 60706-180
225 SOUTH CORDOVA AVE LE CENTER MN 56057 1-507-357-6831 60706-180 0310-00