Cut Sheet
Surge Protection Circuitry Single Stage
UL1449 Voltage Protection Rating 600 Volts
Maximum Surge Current 36,000 Amps (12,000 Amps L-N, 12,000 Amps L-G, 12,000 Amps N-G)
Noise Reduction +35 dB
R
esponse Time Less than 1 nanosecond
Product Warranty 5-Year
Catalog No./ Description/
Item Specifications
4810BCS/ CabinetMATE Surge
4810BDS Protector – Ten
outlets. 6' [1.8m] or
15' [4.6m] cord.
Length 48" [1.2m].
C
atalog No./ Description/
Item Specifications
7712BCS/ CabinetMATE Surge
7712BDS Protector – Twelve
outlets. 6' [1.8m] or
15' [4.6m] cord.
Length 77" [2m].
C
atalog No./ Description/
Item Specifications
7011BCS/ CabinetMATE Surge
7011BDS Protector – Eleven
outlets. 6' [1.8m] or
15' [4.6m] cord.
Length 70" [1.8m].
15A CabinetMATE Surge Protector Ordering Information
CabinetMATE Surge Protector Specifications
j
j
j
CabinetMATE Surge Protectors
WHY DON’T WE SPECIFY JOULES?
The Joule rating does not provide an accurate indication of the robustness of a surge suppressor. The Joule rating is energy over time and it is
very easy to artificially inflate the Joule rating by changing the time base. The Institute of Electrical and Electronics Engineers (IEEE) as well as
the National Electrical Manufacturers Association (NEMA) both warn against using Joules to compare surge suppressors.
A much better indication of the robustness of a surge suppressor is the Nominal Discharge Current (I
n
). The Nominal Discharge Current is a
rating of the current surge current the surge suppressor can handle for 15 surges and still remain functional. This rating is independently
verified by Underwriters Laboratories (UL) and the rating is required to be marked on the surge suppressor.
In fact, UL requires that the surge suppressor must have an I
n
rating of 3kA or it is not suitable for installation closer than 30 feet [10m] from the
service entrance. All of our surge suppressors have an I
n
rating of 3kA and can be used anywhere in the building.
When comparing surge suppressors, don’t be fooled by the Joule game. Look for an I
n
rating of 3kA to be sure you are getting the best in
surge suppression.