Installation Manual

TPB
COMMUNICATIONS
(small compt.)
POWER
(large compt.)
AMTC-ACT
25DTC-ACT
AMDTP-L
25DTP
AMDTP-A
25DTP-A
(1.40" [35.56mm])
AMDTP-B
25DTP-B
25DTC-CVR AMTC-CVR
1"
[25.4mm]
2 1/4"
[57.15mm]
1 1/4"
[31.75mm]
2 5/16"
[58.74mm]
25DTC-4*, 25DTP-4, 25DTP-4ACT,
AMTC-4*, AMDTP-4
25DTP-4
AMDTP-4
25DTC-4*
AMTC-4*
Cable Cable Wire/Size O.D. AMDTP 25DTP AMTC & 25DTC Series*
Type Description (inches) (mm) Series Series Small Compt. Large Compt.
40% FILL 40% FILL 40% FILL 40% FILL
THHN / THWN 10 Awg 0.16 4.17 10 10 34 44
12 Awg 0.13 3.30 15 15 54 69
Cable Cable Wire/Size O.D. AMDTP 25DTP AMTC & 25DTC Series*
Type Description Series Series Small Compt. Large Compt.
(inches) (mm) 20% FILL 40% FILL 20% FILL 40% FILL 20% FILL 40% FILL 20% FILL 40% FILL
Unshielded Cat. 5 UTP 0.22 5.59 10 19 10 19 10 19 13 26
Twisted Pair Cat. 3 UTP 0.19 4.83 13 25 13 25 13 25 17 35
2 Pair 0.14 3.56 23 47 23 47 23 47 32 64
Telephone 3 Pair 0.15 3.81 20 41 20 41 20 41 28 56
4 Pair 0.19 4.83 13 25 13 25 13 25 17 35
25 Pair 0.41 10.41 353 535 4 7
RG58/U 0.20 4.95 12 24 12 24 12 24 17 33
Coaxial RG59/U 0.24 6.15 8 16 8 16 8 16 11 21
RG62/U 0.24 6.15 8 16 8 16 8 16 11 21
RG6/U 0.27 6.86 6 13 6 13 6 13 9 17
TwinAxial 100 Ohm 0.33 8.38 484 848 612
Shielded Type 1 STP 0.39 9.91 363 636 4 8
Twisted Pair Type 2 STP 0.47 11.81 242 424 3 6
Type 3 STP 0.25 6.22 8 15 8 15 8 15 10 21
Fiber ZipCord 0.11 2.79 38 76 38 76 38 76 52 104
Fiber Optic Round Fiber 2 Strand 0.18 4.57 14 28 14 28 14 28 19 39
Round Fiber 4 Strand 0.19 4.83 13 25 13 25 13 25 17 35
Round Fiber 6 Strand 0.21 5.33 10 21 10 21 10 21 14 29
* 25DTC/AMTC Series not intended for combining power and communications in the same channel.
RACEWAY WIRE AND CABLE FILL CAPACITIES FOR TELE-POWER POLES - COMMUNICATIONS
RACEWAY WIRE AND CABLE FILL CAPACITIES FOR TELE-POWER POLES - POWER
WIREMOLD
U.S. and International:
60 Woodlawn Street West Hartford, CT 06110
1-800-621-0049 FAX 860-232-2062 Outside U.S.: 860-233-6251
Canada:
570 Applewood Crescent Vaughan, Ontario L4K 4B4
1-800-723-5175 FAX 905-738-9721
© Copyright 2012 Legrand/Wiremold All Rights Reserved
41575R3 0312
Legrand/Wiremold electrical systems conform to and
s
hould be properly grounded in compliance with
requirements of the current National Electrical Code or
c
odes administered by local authorities.
All electrical products may present a possible shock or fire
h
azard if improperly installed or used. Legrand/Wiremold
electrical products may bear the mark of a Nationally
R
ecognized Testing Laboratory (NRTL) and should be
i
nstalled in conformance with current local and/or the
National Electrical Code.
25DTC/AMTC & 25DTP/AMTP
Series Tele-Power
®
Poles
I N S T A L L A T I O N I N S T R U C T I O N S
Installation Instruction No.: 41573R3 Updated March 2012

Summary of content (2 pages)