LISTED
NO. OF CONDUCTORS
WIRE SIZE O.D. Comp. Comp. Max. (Both
THHN/THWN Inches [mm] A B
1
Channels)
2
POWER WIRING 14 AWG 0.111 [2.8] 33 33 40
WITHOUT DEVICES 12 AWG 0.130 [3.3] 42 31 52
10 AWG 0.164 [4.2] 22 20 37
8 AWG 0.216 [5.5] 19 11 24
6 AWG 0.254 [6.5] 11 8 14
60N2 RACEWAY WIRE FILL CAPACITIES FOR POWER
Section A
4.31 in.
2
[2780mm
2
]
Section C
4.31 in.
2
[2780mm
2
]
Section B
1.06 in.
2
[680mm
2
]
5 1/4"
[133mm]
2"
[51mm]
1. Cross-sectional area reduced due to 60N2F55 C-Box.
2. No. of conductors are reduced when using both channels for power.
3. 20% cable fill calculated to approximate reduction in cable capacity due to connectors mounted
within raceway and fittings that may restrict cross-sectional area.
4. 40% cable fill is the maximum designed cable fill based on TIA/EIA 569-A.
O.D. (Approx. Dia.)
CABLE/WIRE SIZE Inches [mm] 20% FILL* 40% FILL**
UNSHIELDED
4-pair, 24 AWG, Cat 3 0.190 [4.8] 30 60
TWISTED PAIR
4-pair, 24 AWG, Cat 5e 0.210 [5.3] 24 49
4-pair, 24 AWG, Cat 6 0.250 [6.3] 17 35
TELEPHONE
2-pair, 24 AWG 0.140 [3.6] 56 112
3-pair, 24 AWG 0.150 [3.8] 48 97
4-pair, 24 AWG 0.190 [4.8] 30 60
25-pair, 24 AWG 0.410 [10.4] 6 13
COAXIAL
RG58/U 0.195 [5.0] 28 57
RG59/U 0.242 [6.1] 18 37
RG62/U 0.242 [6.1] 18 37
RG6/U 0.270 [6.9] 15 30
TWINAXIAL
100 Ohm 0.330 [8.4] 10 20
SHIELDED
TYPE 1 0.390 [9.9] 7 14
TWISTED PAIR
TYPE 2 0.465 [11.8] 5 10
TYPE 3 0.245 [6.2] 18 36
FIBER
Mini ZipCord 0.079 x 0.157 [2 x 4] 69 139
ZipCord 0.118 x 0.236 [3 x 6] 31 62
Round 4 Strand Fiber 0.187 [4.8] 31 62
Round 6 Strand Fiber 0.256 [6.5] 16 33
60N2 RACEWAY WIRE FILL CAPACITIES FOR COMMUNICATIONS