Cut Sheet

5
Without Device Plate
WIRE SIZE THHN, THWN
10 AWG 12
12 AWG 20
14 AWG 24
ACCESS 5000 RACEWAY WIRE CAPACITIES FOR POWER/TOP COMPARTMENT
ACCESS 5000 RACEWAY SYSTEM PRODUCT APPLICATIONS
CABLE/WIRE SIZE O.D.
Bottom Compartment Top Compartment
Inches [mm] 20% Fill 40% Fill 20% Fill 40%Fill
UNSHIELDED 4-pair, 24 AWG Cat 5 UTP 0.220 5.5 7 14 10 20
TWISTED PAIR 4-pair, 24 AWG Cat 3 UTP 0.190 4.8 9 19 13 27
TELEPHONE 2-pair, 24 AWG 0.140 3.5 18 36 25 50
3-pair, 24 AWG 0.150 3.8 15 31 21 43
4-pair, 24 AWG 0.190 4.8 9 19 13 27
25-pair, 24 AWG 0.410 10.3 2 4 2 5
COAXIAL RG58/U 0.195 4.7 9 18 13 26
RG59/U 0.242 6.1 6 12 8 16
RG62/U 0.242 6.1 6 12 8 16
RG6/U 0.270 6.8 4 9 6 13
TWINAXIAL 100 Ohm 0.330 8.3 3 6 4 9
SHIELDED TYPE 1 0.390 9.8 2 4 3 6
TWISTED PAIR TYPE 2 0.465 11.6 1 3 2 4
TYPE 3 0.245 6.1 5 11 8 16
FIBER OPTIC Two Strand (Duplex) 0.19 4.8 9 19 13 27
Multimode, 62.5/125 ¨µm
ACCESS 5000 RACEWAY CABLE FILL CAPACITIES FOR DATA/COMMUNICATION
A– 5010A Entrance End Feed
B– 5007C-2A Deep Device Bracket
C– 2A Activate Connectivity Insert
D– 5017B, 5017C Internal Base Elbow,
Internal Cover Elbow
E–5007C-1A Device Bracket
F–5010R Right End Cap
G– 5010L Left End Cap
H– 5018B, 5018C External Base Elbow,
External Cover Elbow
A
Back Feed Position
D
E
F
G
NOTE: Illustration is for showing product applications only.
B
C
H
.96"
[24mm]
.74"
[19mm]
* 20% cable fill is calculated to approximate reduction in cable capacity due to connectors mounted within
raceway and fittings that may restrict cross sectional area.
** 40% cable fill is the maximum designed cable fill based on a proposal revision to TIA/EIA-569-A.
5.78"
[147mm]
5.14"
[131mm]
2.77"
[70mm]
2.01"
[51mm]
5.05"
[128mm]