Cut Sheet

2
5410DFO
5406T
5400TC
5400TWC
5418
5418FO
5417FO
5474
5415
5400C
2A Communication
Devices
5406A
5450
5411FO
5410
5450A3
5400TB
5450T
NOTE: Illustration is for showing product applications only.
5400 Series Raceway System Layout
WIRE SIZE O.D. (Approx. Dia.) NO. OF CONDUCTORS
CABLE/WIRE SIZE Inches (mm) COMP. A COMP. B*
POWER WIRING 14 AWG 0.111 (2.8) 50 50
WITHOUT DEVICES 12 AWG 0.130 (3.3) 34 34
10 AWG 0.164 (4.2) 60 60
8 AWG 0.216 (5.5) 21 21
6 AWG 0.254 (6.5) 19 19
POWER WIRING 14 AWG 0.111 (2.8) 50 50
WITH DEVICES 12 AWG 0.130 (3.3) 34 34
10 AWG 0.164 (4.2) 60 60
8 AWG 0.216 (5.5) 21 21
6 AWG 0.254 (6.5) 19 19
5400TB Series Raceway Wire Fill Capacities for Power
O.D. (Approx. Dia.) COMP. A
CABLE/WIRE SIZE Inches (mm) 40% FILL*
UNSHIELDED 4-pair, 24 AWG Cat 3 0.190 (4.8) 52
TWISTED PAIR 4-pair, 24 AWG Cat 5e 0.210 (5.3) 42
4-pair, 24 AWG Cat 6 0.250 (6.3) 30
4-pair, 24 AWG Cat 6a** 0.250 (6.3) 15
25-pair, 24 AWG 0.250 (6.3) 11
COAXIAL RG6/U 0.270 (6.9) 26
FIBER ZipCord 0.118 x 0.236 (3 x 6) 53
Round 4-Strand Fiber 0.187 (4.8) 54
Round 6-Strand Fiber 0.256 (6.5) 28
5400TB Series Raceway Wire Fill Capacities for Communications
5400T Series Raceway & MXN Series Raceway Wire Fill Capacity Charts
* Wire fill capacity is reduced to allow for proper conductor bend radius and maximum
permissible heat rise.
** Category 6 augmented (6a) cable for 10 gigabit Ethernet – maximum allowed cable diameter
per addenda No. 11 ANSI TIA/EIA 568-B.2.
* Total raceway capacity not to exceed capacity specified in Compartment B.
Download this product’s PEP ecopasport
®
environmental product declaration at
www.legrand.us/resources-and-downloads.
This declaration conforms with ISO 14025 and
14040 and is in alignment with EN 15804.